PACi NX Ð Setup Low Temperature
Next, we need to change the 4 codes below:
Code no: 11 - Indoor capacity size, change to indoor capacity required. (See table below)
Code no: 1F - Upper setpoint limit, default 0030 (30°C), change to 0024 (24°C)
Code no: 20 - Lower setpoint limit data 0018 (18°C), change to 0010 (10°C)
Code no: 0F - Cool only data 0000 (heat pump), change to 0001 (cooling only).