PACi Elite R32 Double Twin Split Ð Pipework
Pipe parameters
Double twin split Ð UÐ
250PZH2E8 (4 X 60 indoor
units)
Total pipe length
Maximum pipe length from
outdoor unit to most distant
indoor unit
L
L2
CZ-P224BK2BM
CZ-P224BK2BM
L + L1 + L3 or L
+ L1 + L4 or L +
L2 + L5 or L + L2
+ L6
< 60m
< 60m
Maximum branch length
L1 + L3 or L1 +
L4 or L2 + L5 or
L2 +L6
< 20m
Maximum branch length
difference
L 2 + L6 (MAX)
L1 + L3 (MIN)
(L2 + L6) - ( L1 +
L3)
L1 : L2 Ð L1
< 10m
Maximum pipe length
differences after second
branch (Double Twin)
L4> L3: L4-L3