PACi Elite R32 Twin Splits Ð Pipework
Pipe sizes
Twin split Ð UÐ
200PZH2E8 (2 X 100
indoor units)
L
L1
1Ó1/8Ó & 3/8Ó
L2
5/8Ó & 3/8Ó
Total pipe length
L + L1 + L2
< 90m
Maximum branch length
L1 or L2
< 20m
L1< L2
L1 Ð L2
< 10m
Height diff, outdoor
above
H1 above
< 30m
Height diff, outdoor
below
H1 below
< 15m
Height diff, indoor to
indoor
Pipe
parameters
H2
< 0.5m
Total pipe length
L + L1 + L2
< 60m
Maximum branch length
L1 or L2
< 20m
L1< L2
L1 Ð L2
< 10m
Height diff, outdoor
above
H1 above
< 30m
Height diff, outdoor
below
H1 below
< 15m
Height diff, indoor to
indoor
H2
< 0.5m
Maximum branch pipe
length difference
L
CZ-P680BK2BM
H1
L2
L1
H2
Pipe sizes
L
1Ó1/8Ó & 1/2Ó
Twin split Ð UÐ
250PZH2E8 (2 X 125
indoor units)
L1
L2
5/8Ó & 3/8Ó
Maximum branch pipe
length difference
L
CZ-P224BK2BM
H1
L1
L2
H2
70
Pipe parameters
Use the main pipe to gain any rise or fall required for the pipes.
" The number of bends should be 8 or less in a single system, and 15 or less overall.
" Branch pipes should be positioned horizontally.