UPDATED A5 Panasonic technical handbook F 2025 - Flipbook - Page 69
PACi Elite R32 Twin Splits Ð Pipework Restrictions
Pipe Size L
Elite Outdoor
Indoor
Units
Liquid in.
(mm)
Gas in.
(mm)
Pipe Size L1 & L2
Liquid in.
(mm)
Gas in.
(mm)
Total Pipe
Length
L + L1 + L2
Outdoor to
furthest Indoor
Max Branch
Length
Max Branch
Length Diff
L1 or L2
L1 > L2 L1 - L2
Maximum Elevation (m)
OD above ID OD lower ID
H1
H1
ID to ID
H2
U-200PZH2E8
2 x 1014
3/8 (9.52) 1 1/8 (28.57) 3/8 (9.52) 5/8 (15.88)
100
90
20
10
30
15
0.5
U-250PZH2E8
2 x 1014
1/2 (12.7) 1 1/8 (28.57) 3/8 (9.52) 5/8 (15.88)
80
60
20
10
30
15
0.5
69