PACi NX Elite Outdoor Unit Specification
Elite Outdoor
U-36PZH3E5
U-50PZH3E5
U-60PZH3E5
U-71PZH4E5/8
U-100PZH4E5/8
U-125PZH4E5/8
U-140PZH4E5/8
Minimum Length Maximum Length
(m)
(m) L
3
3
3
5
5
5
5
Pre-Charged
Length (m)
Additional
Charge g/m
30
30
30
30
30
30
30
15
15
15
30
40
40
40
40
40
40
60
85
85
85
Max running current:
36 = 11amps
50 = 12amps
60 = 16.4amps
71 = 20.4 amps Ð 3ph = 6.9amps
100 = 28.3amps Ð 3ph = 9.9amps
125 = 32.7amps Ð 3ph = 11.4amps
140 = 32.7amps Ð 3ph = 11.4amps
58
Maximum Elevation (m)
OD above ID OD lower ID
H1
H1
30
15
30
15
30
15
30
15
30
15
30
15
30
15
Liquid in. (mm)
Gas in. (mm)
Factory Charge
(kg)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
1/2 (12.7)
1/2 (12.7)
1/2 (12.7)
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
1.13
1.13
1.15
1.95
2.70
3.00
3.00
Suggested fuse size:
36 = 13amp
50 = 16amp
60 = 20amp
71 = 25amp Ð 3ph =10amp
100 = 32amp Ð 3ph = 13amp
125 = 40amp Ð 3ph = 13amp
140 = 40amp Ð 3ph = 13amp