UPDATED A5 Panasonic technical handbook F 2025 - Flipbook - Page 29
RAC Professional Inverter R32 YKEA Specs
POWER
MAX CURRENT:
Z25 = 5.6A
Z50 = 10.5A
Z35 = 6.6A
Z71 = 14.7A
Z42 = 8.1A
Built in
SUGGESTED FUSE SIZE:
Z25 = 10A
Z50 = 16A
Z35 = 10A
Z71 = 20A
Z42 = 10A
29
3 CORE & EARTH
Model
Duty
Cooling / Heating
Pipe sizes
Outdoor
above
Outdoor
below
Factory charged
With / For
Additional
charge
Min / Max Pipe
run
CS-Z25YKEA
2.5 kw / 3.4 kw
1/4Ó & 3/8Ó
15m
15m
0.89 kg for 7.5m
10 g/m
3m / 20m
CS-Z35YKEA
3.5 kw / 4.0 kw
1/4Ó & 3/8Ó
15m
15m
0.89 kg for 7.5m
10 g/m
3m / 20m
CS-Z42YKEA
4.2 kw / 5.3 kw
1/4Ó & 1/2Ó
15m
15m
0.97 kg for 7.5m
10 g/m
3m / 20m
CS-Z50YKEA
5.0 kw / 5.8 kw
1/4Ó & 1/2Ó
15m
15m
1.13 kg for 7.5m
15 g/m
3m / 30 m
CS-Z71YKEA
7.1 kw / 8.2 kw
1/4Ó & 5/8Ó
20m
20m
1.35 kg for 10m
25 g/m
3m / 30m