RAC R32 TZ Multi Inverter Systems (2-port)
CU-2TZ41TBE / 2TZ50TBE : INVERTER MULTI SYSTEM
PIPING PARAMETERS
MIN / MAX Distance to indoor unit
3m / 20m
Max lift - Outdoor unit above
10m
Max lift - Outdoor unit below
10m
Max system total piping
30m
Minimum of 2 indoor units must be
connected
Factory charged for 20m with 0.9kg R32- Additional charge 15
g/m
Power supply 220-240V/1Ph/50Hz
PIPE SIZES
Suggested fuse size 16 amp
Stub ÒAÓ
3/8Ó (9.52mm)
1/4Ó (6.35mm)
Stub ÒBÓ
3/8Ó (9.52mm)
1/4Ó (6.35mm)
" If the Gas pipe connection of the indoor unit is larger
than the gas pipe connection of the outdoor unit,
" Run the gas pipe in the size of the indoor unit and
reduce at the outdoor unit.