RAC R32 Free Multi Inverter Systems (5-port)
CU-5Z90TBE : INVERTER MULTI SYSTEM
PIPING PARAMETERS
MIN / MAX Distance to indoor unit
3m / 25m
Max lift - Outdoor unit above
15m
Max lift - Outdoor unit below
15m
Height diff between indoor units
25m
Max system total piping
80m
CU-5Z90TBE
Minimum of 2 indoor units
must be connected.
Factory charged for 45m with 2.72kg R32- Additional charge 20 g/m
PIPE SIZES
Stub ÒAÓ
3/8Ó (9.52mm)
1/4Ó (6.35mm)
Stub ÒBÓ
3/8Ó (9.52mm)
1/4Ó (6.35mm)
Stub ÒCÓ
3/8Ó (9.52mm)
1/4Ó (6.35mm)
Stub ÒDÓ
3/8Ó (9.52mm)
1/4Ó (6.35mm)
Stub ÒEÓ
3/8Ó (9.52mm)
1/4Ó (6.35mm)
Power supply 220-240V/1Ph/50Hz
Starting current 5 amps
Suggested fuse size 25 amp
" If the Gas pipe connection of the indoor unit is larger
than the gas pipe connection of the outdoor unit,
" Run the gas pipe in the size of the indoor unit and
reduce at the outdoor unit.
If floor standing units are used on multi split above a 2 per port, the installer
needs to check the floor area required.
The installation needs to comply with DIN EN378-1:2018-04