Detailed Setting Codes
DN
Description
Comment
Initial value
1b
(1B)
Forced thermo ON time
Compressor run time
0
1E
Temperature shift for cooling/heating change
in auto heat/cool mode
0
1F
Upper limit temp setting of cooling
30
20
Lower limit temp setting of cooling
18
21
Upper limit temp setting of heating
30
22
Lower limit temp setting of heating
23
Upper limit temp setting of drying
24
Lower limit temp setting of drying
18
25
Upper limit temp setting of auto mode
27
26
Lower limit temp setting of auto mode
17
28
Restart after power failure
2A
Filter (CN70) input switching
Change to remote control temperature
setting range
16
30
0
2
Setting
Option
0000
0001
0001
0002
0007
0018
0030
0018
0030
0018
0030
0016
0030
0018
0030
0018
0030
0017
0027
0017
0027
0000
0001
5-minutes
4-minutes
±1¡C
±2¡C
±7¡C
18¡C
30¡C
18¡C
30¡C
18¡C
30¡C
16¡C
30¡C
18¡C
30¡C
18¡C
30¡C
17¡C
27¡C
17¡C
27¡C
Normal
Auto restart
0000
Filter input (differential pressure switch input)
0001
Alarm input
Humidifier input (Operates linked with drain
pump when humidifier is ON)
Yes
None
0002
2C
185
Indoor unit Electronic Expansion Valve
(MOV)
0
0000
0002