UPDATED A5 Panasonic technical handbook F 2025 - Flipbook - Page 184
Detailed Setting Codes
DN
12
13
14
Comment
Outdoor Unit Address
Indoor Unit Address
Group control address
Initial value
99
Settings are 0001 to 0030. (May be set
manually by local connection of wired
controller)
99
Settings are 0001 to 0030. (May be set
manually by local connection of wired
controller)
99
Cooling Intake Temperature Shift
Range -10 to 10K
0
18
Automatic stop time after operation start
Can be set in 5-minute units
0
Flap setting
Setting
Option
0001
0002
0003
Unit 1
Unit 2
Unit 3
0030
0099
0001
0002
0003
Unit 30
Not Set
Unit 1
Unit 2
Unit 3
0064
0099
0000
-010
0000
0010
0000
0001
Unit 30
Not Set
Individual Unit
Main unit (One of the group-control indoor
units)
Subunit (All group-control indoor units except
for main unit)
Intake temperature 10¡C down.
No intake temperature shift
Intake temperature 10¡C up
Disabled
5-minutes
0125
0000
0001
0002
0003
0004
625-minutes
No Flap
Only Swing
1 direction type
2 direction type
4 direction type
0001
0002
17
19
184
Description
4