Detailed Setting Codes
181
DN
Description
Comment
Initial value
01
Filter sign ON time
Filter sign displayed after selected time has
elapsed Ð or by external pressure switch
(CN70)
0002
02
Degree of filter fouling
Allows filter alarm time to be halved if used in
a dirty environment
0000
03
Central control address
When under network (central) control.
0099
04
Operating mode priority change
Used with heat pump VRF system Ð priority
unit determines operating mode.
0000
05
Fan speed when heating thermo OFF
Automatic setting when unit type is set
*PAC-I, ECO-iÿ02
*GHPÿ00
0
Setting
0000
0001
0002
0003
0004
0005
0000
0001
0001
0002
0003
0063
0064
0099
0000
0001
0000
0001
0002
0003
0004
0005
0006
0007
0008
0009
0010
0011
0012
0013
0014
0015
Option
Not Displayed
150 hours
2500 hours
5000 hours
10000 hours
For dirt sensor
Standard
Dirty Environment
Central control address 1
Central control address 2
Central control address 3
Central control address 63
Central control address 64
No Central control address set
Normal
Priority
Comp ON = L: 1min, LL: 3min
Comp ON = L
Comp ON = LL
Comp ON = Stop
Comp ON = L: 1min, LL: 3min
Comp ON = L
Comp ON = LL
Comp ON = Stop
Comp ON = L: 1min, LL: 3min
Comp ON = L
Comp ON = LL
Comp ON = Stop
Comp ON = LL: 1min, Stop: 3min
Comp ON = LL: 1min, Stop: 3min
Comp ON = L: 1min, Stop: 3min
Comp ON = L: 1min, Stop: 3min