Outdoor Unit Maintenance Controller RTC 2/4 Only
OUTDOOR UNIT FAN CONTROL
High Static Pressure Mode
MF3
ûThe outdoor unit allows a high static pressure changing the settings.
ûThe maximum permissible static pressure is 80Pa.
ûThe system becomes to the High static pressure mode by setting in the outdoor unit.
ûEEPROM setting in outdoor unit, CODE : 8F
NOT
E
When EEPROM CODE : 8F is set from 0 to 1 or 2,
The maximum permissible static pressure is 80Pa.
Setting No. 3 to 6 is no use.
137
Normal fan static operation (30 Pa) (Factory setting).