UPDATED A5 Panasonic technical handbook F 2025 - Flipbook - Page 107
R410A Mini ECOi LE1 Pipework Lengths (8HP & 10HP)
Total pipe length f 300m
MAX tubing length
Actual
f
150m
Equivalent
f
175m
Elevation
f 50m when OD is above ID
f 40m when OD is lower than
ID
Difference between MAX length and MIN
length from the 1ST distribution joint
L2-L4 f 50m
MAX height difference
between ID units f
15m
MAX f 50m branch length
107