UPDATED A5 Panasonic technical handbook F 2025 - Flipbook - Page 106
R410A Mini ECOi LE2 Pipework Lengths (4HP Ð 6HP)
Total pipe length 180m
MAX tubing length
Actual
f 150m
Equivalent
f 175m
Elevation
f 50m when OD is above ID
f 40m when OD is lower than ID
Difference between MAX length and MIN
length from the 1ST distribution joint
L2-L4 f 50m
MAX height difference
between ID units f 15m
MAX 50m branch length
106