UK VRF GEN 24 - Flipbook - Page 96
GENERAL INDEX
NEW AHU connection kit MAH4M for ECOi 2-Pipe
Space-saving compact casing.
Direct Modbus communication without the need for an additional interface.
Accurate control with a pressure transducer.
New
2024
Built-in controller.
PAW-P+100MAH4M
6 HP
12 HP
16 HP
Cooling capacity
Nominal
kW
16,0
33,5
45,0
Heating capacity
Nominal
kW
17,0
37,5
50,0
Air flow
Min / Max
m³/h
1 800 / 4 400
2 000 / 10 000
3 500 / 12 000
Dimension
HxWxD
mm
300 x 400 x 150
300 x 400 x 150
300 x 400 x 150
Tentative data
Weight
kg
11
11
11
Pipe length range
m
10 ~ 100
10 ~ 100
10 ~ 100
Elevation difference (in / out)
Piping diameter ≤ 90 m
Piping diameter > 90 m
m
Liquid
1)
10
10
10
Inch (mm)
3/8 (9,52)
1/2 (12,70)
1/2 (12,70)
1 1/8 (28,57)
Gas
Inch (mm)
5/8 (15,88)
1 (25,40)
Liquid
Inch (mm)
—
5/8 (15,88)
5/8 (15,88)
Gas
Inch (mm)
—
1 1/8 (28,57)
1 1/4 (31,75)
1) For R410A models only.
AHU connection kit / system combination
Cooling capacity
Mini VRF
Mini ECOi LZ2 Series (R32)
Mini ECOi LE2 Series (R410A)
AHU connection kit
EEV pack
6 HP
16,0 kW
U-5LZ2E5(8)
U-6LZ2E5(8)
U-5LE2E5(8)
U-6LE2E5(8)
—
PAW-P+100MAH4M
PAW-P+116EEVPACK
12 HP
33,5 kW
U-8LZ2E8
U-10LZ2E8
U-8LE1E8
U-10LE1E8
U-8ME2E8
U-10ME2E8
U-12ME2E8
PAW-P+100MAH4M
PAW-P+133EEVPACK
16 HP
45,0 kW
—
—
U-14ME2E8
U-16ME2E8
PAW-P+100MAH4M
PAW-P+145EEVPACK
Accessories
Accessories
PAW-P+102SENSPACK
AHU connection kit sensor pack 1 (2 pcs of SENSOR
PT1000 HT IP67 -50/250 CABLE 6 m PCK)
PAW-P+116EEVPACK
EEV pack 1 (1 pc of expansion valve ≤ 16 kW (R410A / R32)
and 1 pc of UNIPOLAR stator)
PAW-P+133EEVPACK
EEV pack 2 (1 pc of expansion valve ≤ 33 kW (R410A / R32)
and 1 pc of UNIPOLAR stator)
Technical focus
· Maximum capacity / system: 16 HP (45 kW*)
· Selectable expansion valve packs depending on the
capacity
· DC 12 V outlet available without optional interface
· Maximum elevation difference indoor/outdoor unit: 10 m
· Elevation difference (indoor unit / indoor unit): 4 m
· In / out connection capacity ratio: 50~100%
· Maximum number of AHU connection kits: 1 unit
· Outdoor temperature range in heating: -20 ~ +15 °C
· Available temperature range for the suction air at AHU
connection kit: cool: +18 ~ +32 °C / heat: +16 ~ +30 °C
· The system’s set temperature can be selected either as
the default setting discharge air temperature (supply
room temperature) or the suction air set temperature (or
room return air temperature)
· Accurate control with a pressure transducer
· Direct Modbus communication with a built-in Modbus
S-Link interface
· Various technical parameters available with Modbus
· SG ready fulfilled. Demand input can be set Thermostat
OFF or 40 – 200% by the user
· Defrost operation signal, compressor status ON / OFF
output
· Display an error message concerning drain water
overflow
96
2-Pipe VRF
ECOi EX ME2 Series
EEV pack 3 (1 pc of expansion valve ≤ 45 kW (R410A / R32)
and 1 pc of UNIPOLAR stator)
PAW-P+145EEVPACK
Remote control pack (1 pc of PGNE 132 x 64 mm,
PAW-P+100PGNEPACK mounting panel and 1 pc of cable L= 1,5 m, telephone
connectors)
· Connectable with S-Link system. Special care for
electrical noise may be necessary depending on the
on-site system
· Fan control signal output to manage the air flow
(ON / OFF)
· Alarm status monitoring output
* Nominal cooling capacity.
9
10
2 3
1
8
4
11
5
6
7
System and regulations. System overview.
1 | AHU Unit equipment (field supplied)
2 | Thermistor for gas pipe (E3)
3 | Pressure transductor
4 | Thermistor for discharge air (BL)
5 | Thermistor for liquid pipe (E1)
6 | Thermistor for suction air (TA)
7 | Expansion valve (accessorie part)
8 | Fan (field supplied)
9 | AHU connection kit controller box
10 | Optional remote controller
11 | Outdoor unit Mini ECOi and 2-Pipe ECOi EX