UK VRF GEN 24 - Flipbook - Page 91
R32
VRF SYSTEMS INDEX
R410A
VRF SYSTEMS
K2 type wall-mounted · R32 / R410A
The wall-mounted unit has a stylish smooth panel that looks good and is easy
to clean.
The unit is also smaller, lighter and substantially quieter than previous models
making it ideal for small offices and other commercial applications.
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
S-15MK2E5B
S-22MK2E5B
S-28MK2E5B
S-36MK2E5B
S-45MK2E5B
S-56MK2E5B
S-73MK2E5B
Cooling capacity
Indoor unit
kW
1,5
2,2
2,8
3,6
4,5
5,6
7,3
10,6
Input power
W
25,00
25,00
25,00
30,00
30,00
35,00
55,00
80,00
Current
A
0,20
0,21
0,23
0,25
0,32
0,35
0,51
0,70
Heating capacity
kW
1,7
2,5
3,2
4,2
5,0
6,3
8,0
11,4
Input power
W
25,00
25,00
25,00
30,00
30,00
35,00
55,00
80,00
Current
A
Fan type
S-106MK2E5B
0,20
0,21
0,23
0,25
0,32
0,35
0,51
0,70
Cross flow
Cross flow
Cross flow
Cross flow
Cross flow
Cross flow
Cross flow
Cross flow
Cool (Hi / Med / Lo)
m³/min
7,9 / 7,4 / 6,5
9,0 / 7,5 / 6,5
9,5 / 8,3 / 6,5
10,9 / 9,0 / 6,5
14,5 / 12,5 / 10,0
16,0 / 14,0 / 12,0
19,5 / 17,0 / 14,0
21,5 / 18,5 / 15,0
Heat (Hi / Med / Lo)
m³/min
9,0 / 7,7 / 6,8
9,2 / 8,3 / 6,8
9,7 / 8,5 / 6,8
11,2 / 9,5 / 6,8
14,5 / 12,5 / 10,0
16,0 / 14,0 / 12,0
19,5 / 17,0 / 14,0
21,5 / 18,5 / 15,0
Sound pressure
Hi / Med / Lo
dB(A)
34 / 32 / 29
36 / 33 / 29
37 / 34 / 29
40 / 36 / 29
38 / 35 / 33
40 / 37 / 35
47 / 44 / 40
49 / 46 / 42
Sound power
Hi / Med / Lo
dB(A)
49 / 47 / 44
51 / 48 / 44
52 / 49 / 44
55 / 51 / 44
53 / 50 / 48
55 / 52 / 50
62 / 59 / 55
64 / 61 / 57
mm
290 x 870
x 214
290 x 870
x 214
290 x 870
x 214
290 x 870
x 214
302 x 1 120
x 236
302 x 1 120
x 236
302 x 1 120
x 236
302 x 1 120
x 236
Air flow
Dimension
HxWxD
Net weight
kg
Piping diameter
9
9
9
9
13
13
14
14
Liquid
Inch (mm)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
3/8 (9,52) 1)
3/8 (9,52)
Gas
Inch (mm)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
5/8 (15,88) 1)
5/8 (15,88)
1) When the piping diameter is (liquid) Ø1/4 (6,35) - (gas) Ø1/2 (12,70), connect the liquid socket tube (Ø1/4 (6,35) - Ø3/8 (9,52)) to the liquid tubing side indoor unit and connect the gas socket tube (Ø1/2 (12,70) Ø5/8 (15,88)) to the gas tubing side indoor unit.
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
PAW-RE2C4-MOD-BK
Room controller for hotel rooms, black
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
PAW-RE2D4-WH
Display control for hotel rooms, white
CZ-RTC6
CONEX wired remote controller (non-wireless), black
PAW-RE2D4-BK
Display control for hotel rooms, black
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
CZ-CENSC1
Econavi energy saving sensor
CZ-RTC5B
Wired remote controller with Econavi function
CZ-P56SVK2
External valve for model sizes 15 to 56
CZ-RWS3
Infrared remote controller
CZ-P160SVK2
External valve for model sizes 60 to 106
CZ-CGLSC1
Panasonic R32 refrigerant leak detector
Technical focus
· Compact lightweight units for easy installation
· Quiet operation
· Smooth and durable design
· Piping outlet in six directions
· Air distribution is automatically altered depending on the
operational mode
Lighter and smaller units
Compact and lightweight
units make for easy
870 mm
installation. When the unit
is turned OFF, the flap closes completely to prevent entry
of dust into the unit and to keep the equipment clean.
290 mm
PAW-RE2C4-MOD-WH Room controller for hotel rooms, white
Piping outlet in six directions
Piping outlet is possible in six
directions of; right, right rear,
right bottom, left, left rear and
left bottom, making the
installation work more flexible.
Air distribution is
automatically altered
depending on the operational
mode of the unit
Zone for
Zone for
cooling
Quiet operation
heating
These units are among the
quietest in the industry, making them ideal for hotels and
hospitals.
External valve (optional)
CZ-P56SVK2 (model sizes 15 to 56).
CZ-P160SVK2 (model sizes 60 1) to 106).
1) When the piping diameter is liquid 1/4 (6,35) and gas 1/2 (12,70),
use CZ-P56SVK2
28%
SELF-DIAGNOSING
AUTOMATIC FAN
HUMIDITY CONTROL
DRY
AUTO-FLAP
CONTROL
AUTOMATIC
RESTART
AIR SWEEP
OPTIONAL WI-FI
BMS
CONNECTIVITY
ECONAVI and INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
91