UK VRF GEN 24 - Flipbook - Page 87
R32
VRF SYSTEMS INDEX
R410A
VRF SYSTEMS
F3 type variable static pressure adaptive duct · R32 / R410A
Design adaptive ducted F3 range.
2 installation possibilities (horizontal / vertical) with high ESP 150 Pa allows for
flexible installation.
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
R32 unit. S-***MF3E5BN
15
22
28
nanoe™ X as a standard.
36
45
56
60
73
90
112
140
160
R410A unit. S-***MF3E5AN
Cooling capacity
kW
1,5
2,2
2,8
3,6
4,5
5,6
6,0
7,3
9,0
11,2
14,0
16,0
Input power
W
60,00
60,00
60,00
60,00
60,00
89,00
79,00
79,00
136,00
265,00
265,00
330,00
Current
A
0,45
0,45
0,45
0,45
0,45
0,63
0,52
0,52
0,90
1,76
1,76
2,14
Heating capacity
kW
1,7
2,5
3,2
4,2
5,0
6,3
7,1
8,0
10,0
12,5
16,0
18,0
Input power
W
60,00
60,00
60,00
60,00
60,00
89,00
79,00
79,00
136,00
265,00
265,00
330,00
Current
A
0,45
0,45
0,45
0,45
0,45
0,63
0,52
0,52
0,90
1,76
1,76
2,14
2
2
2
2
2
2
2
2
2
2
2
2
Fan type
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
Sirocco
fan
nanoe X Generator
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
External static pressure
Pa
30
(10-150)
30
(10-150)
30
(10-150)
30
(10-150)
30
(10-150)
30
(10-150)
30
(10-150)
30
(10-150)
40
(10-150)
50
(10-150)
50
(10-150)
50
(10-150)
Air flow 2)
m³/min
12,8/11,0/ 12,8/11,0/ 14,0/12,0/ 14,0/12,0/ 14,0/12,0/ 16,0/14,0/ 21,0/18,0/ 21,0/18,0/ 25,0/23,0/ 37,0/32,0/ 37,0/32,0/ 40,0/34,0/
8,0
8,0
8,0
8,0
8,0
10,0
15,0
15,0
16,0
26,0
26,0
28,0
R32 leakage sensors 1)
Sound pressure
Hi /
Med /
Lo
dB(A)
31 / 28 / 20 31 / 28 / 20 31 / 28 / 20 31 / 28 / 20 31 / 28 / 20 35 / 32 / 24 31 / 28 / 23 31 / 28 / 23 35 / 33 / 25 41 / 36 / 32 41 / 36 / 32 43 / 37 / 33
Sound power
dB(A)
54 / 51 / 43 54 / 51 / 43 54 / 51 / 43 54 / 51 / 43 54 / 51 / 43 58 / 55 / 47 54 / 51 / 46 54 / 51 / 46 58 / 56 / 48 64 / 59 / 55 64 / 59 / 55 66 / 60 / 56
Dimension (H x W x D)
mm
250 x 800
x 730
Net weight
kg
250 x 800
x 730
250 x 800
x 730
250 x 800
x 730
250 x 800
x 730
250 x 800
x 730
250 x 1000 250 x 1000 250 x 1000 250 x 1400 250 x 1400 250 x 1400
x 730
x 730
x 730
x 730
x 730
x 730
26
26
26
26
26
26
31
31
31
40
40
40
Piping diameter
R32 model
Liquid
Inch (mm)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas
Inch (mm)
1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
Piping diameter
R410A model
Liquid
Inch (mm)
1/4 (6,35)
Gas
Inch (mm)
1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 1/2 (12,70) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88) 5/8 (15,88)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
1) Only available in the R32 version. 2) Value referred to standard settings at shipment (H curve 8, M curve 5, L curve 1).
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
PAW-RE2C4-MOD-BK
Room controller for hotel rooms, black
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
PAW-RE2D4-WH
Display control for hotel rooms, white
CZ-RTC6
CONEX wired remote controller (non-wireless), black
PAW-RE2D4-BK
Display control for hotel rooms, black
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
CZ-CENSC1
Econavi energy saving sensor
CZ-RTC5B
Wired remote controller with Econavi function
PAW-APF800F
NEW BION air pollutant filter for MF3 15, 22, 28, 36, 45 and 56
CZ-RWS3 + CZ-RWRC3 Infrared remote controller and receiver
PAW-APF1000F
NEW BION air pollutant filter for MF3 60 and 73
PAW-RE2C4-MOD-WH Room controller for hotel rooms, white
PAW-APF1400F
NEW BION air pollutant filter for MF3 90, 106, 112, 140 and 160
Technical focus
· 4 installation possibilities with horizontal and vertical
mounting, plus selectable rear or bottom air inlet
· Industry leading low noise with super quiet operation,
minimum 20 dB(A)
· Only 250 mm height and lightweight unit from, 26 to 40 kg
· Integrated Panasonic R32 refrigerant leak detectors 1)
· Improved drain pan suitable for both horizontal / vertical
installation
· Drain pump included 2)
· nanoe™ X (Generator Mark 3: 48 trillion hydroxyl
radicals/sec) as standard, effective even with duct
connections up to 10 m with 3 x 90° bends 3)
· New BION air pollutant filter for certain types of
pollutants, such as nitrogen dioxide (NO2), nitrogen
oxides (NOX) and Ozone (O3) (optional)
Vertical Installation
Vertical installation option. Variable
external static pressure to support
ducted installations with bends.
* Vertical installation requires additional settings on field, please
check the installation manual.
Improved drain pan design
Drain pan is shared in both
cases horizontal and vertical
installation.
No need to modify the unit.
Horizontal
Shared
drain pan
Vertical
1) Only available in the R32 version. 2) For use with horizontal installation only. 3) Panasonic
internal survey.
28%
FILTER INCLUDED
SELF-DIAGNOSING
AUTOMATIC FAN
HUMIDITY CONTROL
DRY
AUTOMATIC
RESTART
BUILT-IN
DRAIN PUMP
OPTIONAL WI-FI
BMS
CONNECTIVITY
ECONAVI and INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
87