UK VRF GEN 24 - Flipbook - Page 83
R32
VRF SYSTEMS INDEX
R410A
VRF SYSTEMS
U2 type 4 way 90x90 cassette · R32 / R410A
The 4 way 90x90 cassettes with integrated nanoe X Generator Mark 3 and
design panel.
A modern flat panel design blends into any space. These cassettes provide high
energy saving, comfort and better indoor air quality that satisfy customers.
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
Indoor unit. S-***MU2E5BN
nanoe™ X as a standard.
22
28
36
45
56
60
73
90
112
140
160
Cooling capacity
kW
2,2
2,8
3,6
4,5
5,6
6,0
7,3
9,0
11,2
14,0
16,0
Input power
W
20,00
20,00
20,00
20,00
25,00
35,00
40,00
40,00
95,00
95,00
105,00
Current
A
0,21
0,21
0,21
0,21
0,23
0,33
0,36
0,38
0,74
0,74
0,82
Heating capacity
kW
2,5
3,2
4,2
5,0
6,3
7,1
8,0
10,0
14,0
16,0
18,0
Input power
W
20,00
20,00
20,00
20,00
25,00
35,00
40,00
40,00
90,00
90,00
100,00
Current
A
Fan type
nanoe X Generator
Air flow
Sound pressure
0,20
0,20
0,20
0,22
0,32
0,35
0,37
0,72
0,72
0,80
Turbo fan
Turbo fan
Turbo fan
Turbo fan
Turbo fan
Turbo fan
Turbo fan
Turbo fan
Turbo fan
Turbo fan
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
Mark 3
m³/min
12,8 / 12,1 / 12,8 / 12,1 / 14,5 / 13,0 / 15,5 / 13,0 / 16,5 / 13,5 / 21,0 / 16,0 / 22,5 / 16,0 / 23,0 / 18,5 / 36,0 / 26,0 / 36,0 / 26,0 / 37,0 / 28,0 /
11,5
11,5
11,5
11,5
11,5
13,0
13,0
14,0
20,0
20,0
24,0
dB(A)
30 / 29 / 28
30 / 29 / 28
30 / 29 / 28
31 / 29 / 28
32 / 30 / 28
36 / 32 / 29
37 / 32 / 29
38 / 35 / 32
45 / 39 / 35
45 / 39 / 35
46 / 40 / 38
dB(A)
45 / 44 / 43
45 / 44 / 43
45 / 44 / 43
46 / 44 / 43
47 / 45 / 43
51 / 47 / 44
52 / 47 / 44
53 / 50 / 47
60 / 54 / 50
60 / 54 / 50
61 / 55 / 53
Indoor
mm
256 x 840
x 840
256 x 840
x 840
256 x 840
x 840
256 x 840
x 840
256 x 840
x 840
256 x 840
x 840
256 x 840
x 840
256 x 840
x 840
319 x 840
x 840
319 x 840
x 840
319 x 840
x 840
Panel
mm
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
33,5 x 950
x 950
Hi /
Med /
Lo
Sound power
Dimension
(H x W x D)
0,20
Turbo fan
Net weight (Panel)
19 (5)
19 (5)
19 (5)
19 (5)
19 (5)
20 (5)
20 (5)
20 (5)
25 (5)
25 (5)
25 (5)
Piping diameter
R32 model
Liquid
kg
Inch (mm)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas
Inch (mm)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
Piping diameter
R410A model
Liquid
Inch (mm)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
3/8 (9,52) 1) 3/8 (9,52) 1) 3/8 (9,52) 1)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas
Inch (mm)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70)
1/2 (12,70) 5/8 (15,88) 1) 5/8 (15,88) 1) 5/8 (15,88) 1) 5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
1) When the piping diameter is (liquid) Ø1/4 (6,35) - (gas) Ø1/2 (12,70), connect the liquid socket tube (Ø1/4 (6,35) - Ø3/8 (9,52)) to the liquid tubing side indoor unit and connect the gas socket tube (Ø1/2 (12,70) Ø5/8 (15,88)) to the gas tubing side indoor unit. * Above values are in the case of nanoe™ X OFF.
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
PAW-RE2D4-WH
Display control for hotel rooms, white
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
PAW-RE2D4-BK
Display control for hotel rooms, black
CZ-RTC6
CONEX wired remote controller (non-wireless), black
CZ-KPU3W
Standard panel
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
CZ-KPU3AW
Econavi exclusive panel
CZ-RTC5B
Wired remote controller with Econavi function
CZ-CENSC1
Econavi energy saving sensor
CZ-RWS3 + CZ-RWRU3W Infrared remote controller and receiver
CZ-FDU3+CZ-ATU2
Fresh air-intake kit
PAW-RE2C4-MOD-WH Room controller for hotel rooms, white
CZ-CGLSC1
Panasonic R32 refrigerant leak detector
PAW-RE2C4-MOD-BK
Room controller for hotel rooms, black
Technical focus
· High performance turbo fan
· Lower noise in low fan operation
· Ceiling height up to 5,0 m
· Industry leading lightweight design
· Econavi: Temperature, humidity and activity sensor
· nanoe™ X (Generator Mark 3: 48 trillion hydroxyl
radicals/sec) as standard for better indoor air quality,
indoor unit internal cleaning with nanoe™ X and dry
operation
· Powerful drain pump gives 850 mm lift
· Fresh air knockout
· Branch duct connection
· High volume fresh air input with optional air-intake
plenum and chamber (CZ-FDU3+CZ-ATU2)
Panel design
Flat design, well-matched with interior aesthetic.
4-way individual flap control.
The drain pipe can be raised to a maximum height of
850 mm from the bottom of the ceiling
Integrated drain pump allows a drain height of 850 mm
making the installation much easier.
A
B
300 mm or less (as short as possible)
A: 850 mm or lower.
B: 666 mm or lower.
* Length of supplied drain pipe=
250 mm.
Bottom of the ceiling board
28%
SELF-DIAGNOSING
AUTOMATIC FAN
HUMIDITY CONTROL
DRY
AUTO-FLAP
CONTROL
AUTOMATIC
RESTART
AIR SWEEP
BUILT-IN
DRAIN PUMP
OPTIONAL WI-FI
BMS
CONNECTIVITY
ECONAVI and INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
83