R410A
GENERAL INDEX
ECOi 2-Pipe with water heat exchanger for chilled and hot water production
Water heat exchanger (WHE) for hydronic applications.
WHE for ECOi systems controlled by a CZ-RTC5B timer remote control.
Energy-efficient capacity control with superior external static pressure is now
ready.
Availability of easy vertical stacking allows installations in a limited space (up to
3 units)*.
Stainless steel plate heat exchanger with anti-freeze protection control.
Change over between heating and cooling operation.
* Stacking kit (PAW-3WSK) is necessary.
Hydrokit with A class water pump
Hydrokit without pump
PAW-250WP5G1
PAW-500WP5G1
PAW-250W5G1
PAW-500W5G1
Cooling capacity (A 35 °C, W 7 °C)
kW
25,0
50,0
Heating capacity
kW
28,0
56,0
Heating capacity (A +7 °C, W 45 °C)
kW
28,0
56,0
COP (A +7 °C, W 45 °C)
W/W
2,97
3,10
Energy efficiency class at 35 °C 1)
ηs,h (LOT1) 2)
Dimension
HxWxD
Net weight
mm
kg
Water pipe connector
Heating water flow (ΔT=5 K. 35 °C)
m³/h
Electric backup heater
kW
A++
A++
152,0%
152,0%
1 000 x 575 x 1 110
1 000 x 575 x 1 110
135 (140 with pump)
155 (165 with pump)
Rp2 Female thread (50A)
Rp2 Female thread (50A)
5,16
10,32
Not equipped
Not equipped
Flow switch
Equipped
Equipped
Water filter
Equipped
Equipped
0,329 / 0,024
0,574 / 0,024
Input power with A class water pump / without pump
kW
Maximum current with A class water pump / without pump
A
Outdoor unit
Sound pressure
dB(A)
Dimension
2,50 / 0,10
U-20ME2E8
56
60
1 842 x 770 x 1 000
1 842 x 1 540 x 1 000
HxWxD
mm
210
375
Liquid
Inch (mm)
3/8 (9,52)
5/8 (15,88)
Gas
Inch (mm)
7/8 (22,22)
1-1/8 (28,58)
Net weight
kg
Piping diameter
1,43 / 0,10
U-10ME2E8
Pipe length range / Pipe length for nominal capacity
m
170 / 7,5
170 / 7,5
Elevation difference (in / out)
m
50 (OU above) 35 (OU below)
50 (OU above) 35 (OU below)
Pre-charged pipe length / Additional gas amount (R410A)
m / g/m
0 < / Refer to manual
0 < / Refer to manual
Refrigerant (R410A) / CO2 Eq.
kg
5,6 (need additional gas amount at site)
9,5 (need additional gas amount at site)
-11 ~ +15 3)
Operating range
Heat Min ~ Max
°C
-11 ~ +15 3)
Water outlet temperature
range
Cool Min ~ Max
°C
+5 ~ +15
+5 ~ +15
Heat Min ~ Max
°C
+35 ~ +45
+35 ~ +45
1) Unit efficiency energy level: Scale from A+++ to D. 2) Seasonal space cooling / heating energy efficiency following COMMISSION REGULATION (EU) 813/2013. 3) With accessory low temperature kit
-25 ~ +15 °C. Available only as a spare part.
Performance calculation in agreement with Eurovent. Sound pressure measured at 1 m from the outdoor unit and at 1,5 m height.
Accessories
PAW-3WSK
Stacking kit for vertically stacking up to 3 WHE (4 pieces per Kit)
Stacking kit PAW-3WSK.
It is possible to stack up to 3
units. When stacking units,
always anchor the bottom unit to
the ground using the anchor
holes.
Technical focus
· Heating, cooling and DHW
· A class water pump included (only in P model)
· Flexible modularity from 25 kW
· Better partial load vs standard chiller system
· Compatible with all centralized controllers
· Maximum distance between outdoor unit and WHE: 170 m
· Maximum hot water outlet temperature: 45 °C
· Minimum chilled water outlet temperature: 5 °C
· Outdoor temperature range in heating mode: -11 °C to
+15 °C (with low temperature kit -25 °C*)
* Available as a spare part.
74