UK VRF GEN 24 - Flipbook - Page 71
R410A
VRF SYSTEMS INDEX
VRF SYSTEMS
2-Pipe Hybrid GHP/EHP
· Extended lifespan with intelligent energy management.
The goal is for the EHP and GHP to work at optimal speeds
· Low energy cost
· Low emissions
Hybrid GHP
HP
Outdoor unit
Voltage
Power supply
V
Phase
Frequency
Hybrid EHP
20 HP
10 HP
U-20GES3E5
U-10MES2E8
220 - 230 - 240
380 - 400 - 415
Single phase
Three phase
Hz
50
50
Cooling capacity
ηs,c (LOT21)
kW
56,0
28,0
Current
A
Input power
Hot water in cooling mode (at 65 °C outlet)
211,8%
275,4%
5,18
10,70 / 10,20 / 9,80
kW
1,12
6,41
kW
26,20
—
Gas consumption cooling
kW
52,10
—
Heating capacity
ηs,h (LOT21)
kW
63,0
31,5
Current
A
Input power
Gas consumption heating
Standard
143,2%
167,6%
4,79
11,10 / 10,50 / 10,10
kW
1,05
6,62
kW
51,10
—
Starting current
A
30
1
Air flow
m³/min
420
224
56
Sound pressure
Normal mode
dB(A)
58
Sound power
Normal mode
dB(A)
80
77
Dimension
HxWxD
mm
2 255 x 1 650 x 1 000
1 842 x 770 x 1 000
Net weight
kg
765
210
Inch (mm)
5/8 (15,88)
3/8 (9,52)
Gas
Inch (mm)
1 1/8 (28,58)
7/8 (22,22)
Balance
Inch (mm)
1/4 (6,35)
1/4 (6,35)
Liquid
Piping diameter 1)
Drain heater
W
Refrigerant (R410A) / CO2 Eq.
kg / T
Maximum allowable indoor / outdoor capacity ratio %
Operating range
40
—
11,05 / 23,0724
5,60 / 11,6928
50 ~ 130
50 ~ 130
Cool Min ~ Max
°C
-10 ~ +43
-10 ~ +43
Heat Min ~ Max
°C
-21 ~ +18
-21 ~ +18
1) Please refer service manual when the maximum piping length exceeds 90 meters (equivalent length).
Technical focus
· 4 settings (economy, efficiency, GHP priority mode, EHP
priority mode)
· DHW energy recovery 26,2 kW (at 65 °C) by engine waste
heat
· Unified refrigerant cycle in GHP and EHP for easy
installation
· DHW priority mode with WHE system
· Connection of up to 48 indoor units
GAS
POWERED
HIGH COP
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
71