UK VRF GEN 24 - Flipbook - Page 67
R410A
VRF SYSTEMS INDEX
VRF SYSTEMS
3-Pipe ECO G GF3 Series
DHW available in all seasons.
Effective production of domestic hot water from engine waste heat
in both heating and cooling, all year round.
HP
16 HP
20 HP
25 HP
U-16GF3E5
U-20GF3E5
U-25GF3E5
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
Single phase
Single phase
Single phase
Hz
50
50
50
Cooling capacity
kW
45,0
56,0
71,0
Refrigeration load Pdesign 1)
ηs,c (LOT21) 1)
kW
Input power
kW
1,17
1,40
1,80
Hot water in cooling mode (at 65 °C outlet)
kW
23,60
27,10
40,50
Gas consumption cooling
Outdoor unit
Voltage
Power supply
V
Phase
Frequency
Heating capacity
56,0
71,0
198,8%
204,9%
kW
45,80
54,80
73,70
Standard
kW
50,0
63,0
80,0
Low temperature
kW
53,0
67,0
78,0
kW
38,0
52,0
60,0
139,2%
140,2%
150,9%
Refrigeration load Pdesign 1)
ηs,h (LOT21) 1)
Input power
Gas consumption heating
45,0
185,2%
Standard
kW
0,56
1,05
0,91
kW
42,20
51,10
68,60
Starter amperes
A
30
30
30
Air flow
m³/min
370
400
460
Sound power
Dimension
Normal
dB(A)
80
81
84
Silent mode
dB(A)
77
78
81
2 255 x 1 650 x 1 000
2 255 x 1 650 x 1 000
2 255 x 2 026 x 1 000
775
775
880
Inch (mm)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
1 1/8 (28,58)
HxWxD
Net weight
mm
kg
Liquid
Piping diameter
Gas
Inch (mm)
1 1/8 (28,58)
1 1/8 (28,58)
Discharge
Inch (mm)
7/8 (22,22)
1 (25,40)
1 (25,40)
Fuel gas
Inch (mm)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
Exhaust drain port
mm
Hot water supply in/out
Elevation difference (in / out)
m
Refrigerant (R410A) / CO2 Eq.
kg / T
Maximum number of connectable indoor units
Operating range
25
25
25
Rp¾ (Nut, thread)
Rp¾ (Nut, thread)
Rp¾ (Nut, thread)
50
50
50
11,50 / 24,00
11,50 / 24,00
11,50 / 24,00
24
24
24
Cool Min ~ Max
°C
-10 ~ +43
-10 ~ +43
-10 ~ +43
Heat Min ~ Max
°C
-21 ~ +18
-21 ~ +18
-21 ~ +18
1) ErP test data.
Hot water take out function added, EU safety regulation standard cleared. 25 HP chassis enlarged due to specification improvement. Pre-coat corrosion fin. Auto Pump Down function.
Solenoid valve kit
KIT-P56HR3
3-Pipe control solenoid valve kit (up to 5,6 kW)
CZ-P56HR3
Solenoid valve kit (up to 5,6 kW)
CZ-CAPE2
3-Pipe control PCB
KIT-P160HR3
CZ-P160HR3
CZ-CAPE2
CZ-CAPEK2 2)
3-Pipe control solenoid valve kit (from 5,6 to 16,0 kW)
Outstanding seasonal energy efficiency, maximum 204,9%
· Capacity ratio 50 ~ 200%
· No defrost cycle
· Maximum total piping length: 780 m
Solenoid valve kit (from 5,6 kW to 16,0 kW)
3-Pipe control PCB
3-Pipe control PCB for wall-mounted
3-Pipe control box kit
CZ-P456HR3
4 ports 3 pipe box (up to 5,6 kW per port)
CZ-P656HR3
6 ports 3 pipe box (up to 5,6 kW per port)
CZ-P856HR3
8 ports 3 pipe box (up to 5,6 kW per port)
CZ-P4160HR3
4 ports 3 pipe box (up to 16,0 kW per port)
Flexible installation
· Full heating capacity down to -21 °C (WB)
· DHW production for all the year
· Connection of up to 24 indoor units
2) Available for S-45/56/73/106MK2E5B.
GAS
POWERED
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
67