UK VRF GEN 24 - Flipbook - Page 64
R410A
GENERAL INDEX
2-Pipe ECO G GE3 Series
The GE3 Series has top level seasonal efficiency in this category.
In addition, this product fits with special needs for commercial
application thanks to DHW priority setting and auto Pump Down
functions.
HP
16 HP
20 HP
25 HP
30 HP
U-16GE3E5
U-20GE3E5
U-25GE3E5
U-30GE3E5
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
Single phase
Single phase
Single phase
Single phase
Hz
50
50
50
50
Cooling capacity
kW
45,0
56,0
71,0
85,0
Refrigeration load Pdesign 1)
ηs,c (LOT21) 1)
kW
Input power
kW
1,17
1,12
1,80
1,80
Hot water in cooling mode (at 65 °C outlet)
kW
23,60
29,10
36,40
46,00
Max COP in hot water
W/W
1,55
1,55
1,49
1,47
Gas consumption cooling
kW
41,10
52,10
67,20
84,10
Standard
kW
50,0
63,0
80,0
95,0
Low temperature
kW
53,0
67,0
78,0
90,0
kW
37,0
53,0
60,0
65,0
150,6%
143,7%
146,9%
151,3%
Outdoor unit
Voltage
Power supply
Frequency
Heating capacity
Refrigeration load Pdesign 1)
ηs,h (LOT21) 1)
Input power
Gas consumption heating
V
Phase
45,0
56,0
71,0
85,0
220,6%
219,3%
240,1%
229,3%
kW
0,56
1,05
0,91
1,75
Standard
kW
38,00
51,10
68,60
75,30
Low temperature
kW
45,40
62,70
60,70
73,90
Starter amperes
A
30
30
30
30
External static pressure
Pa
10
10
10
10
Air flow
m³/min
370
420
460
460
Sound power
Dimension
Normal
dB(A)
80
80
84
84
Silent mode
dB(A)
77
77
81
81
2 255 x 1 650 x 1 000
2 255 x 1 650 x 1 000
2 255 x 2 026 x 1 000
2 255 x 2 026 x 1 000
765
765
870
880
HxWxD
Net weight
Piping diameter
mm
kg
Liquid
Inch (mm)
1/2 (12,70)
5/8 (15,88)
5/8 (15,88)
3/4 (19,05)
Gas
Inch (mm)
1-1/8 (28,58)
1-1/8 (28,58)
1-1/8 (28,58)
1-1/4 (31,75)
Fuel gas
Inch (mm)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
3/4 (19,05)
Exhaust drain port
mm
25
25
25
25
Rp¾ (Nut, thread)
Rp¾ (Nut, thread)
Rp¾ (Nut, thread)
Rp¾ (Nut, thread)
Hot water supply in/out
Elevation difference (in / out)
Refrigerant (R410A) / CO2 Eq.
kg / T
50
50
50
50
11,50 / 24,00
11,50 / 24,00
11,50 / 24,00
11,50 / 24,00
Maximum number of connectable indoor units
Operating range
26
33
41
50
Cool Min ~ Max
°C (DB)
-10 ~ +43
-10 ~ +43
-10 ~ +43
-10 ~ +43
Heat Min ~ Max
°C (WB)
-21 ~ +18
-21 ~ +18
-21 ~ +18
-21 ~ +18
1) ErP test data.
Hot water take out function added, EU safety regulation standard cleared. 25 HP chassis enlarged due to specification improvement. Pre-coat corrosion fin. Auto Pump Down function.
Technical focus
· Superior seasonal energy efficiency, maximum 240,1%
· DHW priority setting
· Operating range in heating down to -21 °C and up to
+24 °C for air to water system
· No defrost cycle
GAS
POWERED
64
· Capacity ratio 50 ~ 200% 1)
· Option of DX or chilled water for indoor heat exchange
· Maximum total piping length: 780 m
1) 50 ~ 200% only when one outdoor unit is installed. In other cases 50 ~ 130%.