UK VRF GEN 24 - Flipbook - Page 51
R410A
VRF SYSTEMS INDEX
HP
Outdoor unit
Voltage
Power supply
V
Phase
VRF SYSTEMS
50 HP
52 HP
54 HP
56 HP
58 HP
60 HP
62 HP
64 HP
U-14ME2E8
U-16ME2E8
U-14ME2E8
U-16ME2E8
U-18ME2E8
U-20ME2E8
U-14ME2E8
U-16ME2E8
U-16ME2E8
U-16ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-16ME2E8
U-16ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-16ME2E8
U-16ME2E8
U-16ME2E8
U-16ME2E8
380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
50
50
50
50
50
50
50
50
Cooling capacity
kW
140,0
145,0
151,0
156,0
162,0
168,0
174,0
180,0
EER 1)
W/W
Frequency
SEER 2)
Three phase
3,55
3,46
3,49
3,41
3,40
3,35
3,60
3,52
6,96
6,72
7,16
6,92
7,30
7,16
6,68
6,55
Current
A
Input power
kW
39,40
41,90
43,30
45,80
47,60
50,10
48,30
51,20
Heating capacity
kW
155,0
160,0
169,0
175,0
182,0
189,0
195,0
201,0
COP 1)
W/W
4,29
4,27
4,11
4,08
4,06
3,94
4,45
4,42
4,08
4,05
4,13
4,07
4,13
4,13
4,11
4,09
SCOP 2)
64,40-61,10-58,90 68,50-65,00-62,70 70,00-66,50-64,10 74,00-70,30-67,80 76,90-73,10-70,40 80,10-76,10-73,40 79,80-75,80-73,00 84,60-80,30-77,40
Current
A
Input power
kW
59,60-56,60-54,60 61,90-58,80-56,70 67,10-63,80-61,50 70,10-66,60-64,20 73,20-69,50-67,00 77,60-73,70-71,00 73,10-69,50-67,00
36,10
37,50
41,10
42,90
44,80
48,00
43,80
76,00-72,20-69,6
45,50
Starting current
A
6,00
6,00
6,00
6,00
6,00
6,00
8,00
8,00
External static pressure (Max)
Pa
80
80
80
80
80
80
80
80
Air flow
m³/min
869
869
1 042
1 042
1 215
1 215
928
928
67,0 / 64,0
Sound pressure
Normal / Silent mode
dB(A)
65,5 / 62,5
65,5 / 62,5
65,0 / 62,0
65,5 / 62,5
64,5 / 61,5
65,0 / 62,0
67,0 / 64,0
Sound power
Normal mode
dB(A)
86,5
86,5
86,0
86,5
85,5
86,0
88,0
88,0
Dimension /
Net weight
HxWxD
mm / kg
1 842 x 4 020
x 1 000 / 1 005
1 842 x 4 020
x 1 000 / 1 005
1 842 x 4 380
x 1 000 / 1 065
1 842 x 4 380
x 1 000 / 1 065
1 842 x 4 740
x 1 000 / 1 125
1 842 x 4 740
x 1 000 / 1 125
1 842 x 4 900
x 1 000 / 1 260
1 842 x 4 900
x 1 000 / 1 260
Liquid
Inch (mm)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
Gas
Inch (mm)
Balance
Inch (mm)
Piping diameter 3)
1-1/2 (38,10) / 1-1/2 (38,10) / 1-1/2 (38,10) / 1-1/2 (38,10) / 1-1/2 (38,10) / 1-1/2 (38,10) / 1-5/8 (41,28) / 1-5/8 (41,28) /
1-5/8 (41,28) 1-5/8 (41,28) 1-5/8 (41,28) 1-5/8 (41,28) 1-5/8 (41,28) 1-5/8 (41,28) 1-3/4 (44,45) 1-3/4 (44,45)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
Refrigerant (R410A) / CO2 Eq.
kg / T
26,10 / 54,4968 26,10 / 54,4968 27,30 / 57,0024 27,30 / 57,0024 28,50 / 59,508 28,50 / 59,508 33,20 / 69,3216 33,20 / 69,3216
Maximum allowable indoor / outdoor
capacity ratio 4)
%
50 ~ 130 (200)
Operating range
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
Cool Min ~ Max
°C
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
Heat Min ~ Max
°C
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
HP
Outdoor unit
Voltage
Power supply
50 ~ 130 (200)
V
Phase
66 HP
68 HP
70 HP
72 HP
74 HP
76 HP
78 HP
80 HP
U-10ME2E8
U-12ME2E8
U-10ME2E8
U-16ME2E8
U-16ME2E8
U-16ME2E8
U-18ME2E8
U-20ME2E8
U-16ME2E8
U-16ME2E8
U-20ME2E8
U-16ME2E8
U-18ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
U-20ME2E8
380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
50
50
50
50
50
50
50
50
Cooling capacity
kW
185,0
190,0
196,0
202,0
208,0
213,0
219,0
224,0
EER 1)
W/W
Frequency
SEER 2)
Three phase
3,52
3,49
3,47
3,42
3,42
3,39
3,38
3,35
6,92
6,91
7,09
6,86
7,03
7,01
7,18
7,16
Current
A
Input power
kW
52,60
54,50
56,50
59,00
60,80
62,90
64,70
66,80
Heating capacity
kW
207,0
213,0
219,0
226,0
233,0
239,0
245,0
252,0
COP 1)
W/W
4,16
4,18
4,05
4,14
4,12
4,03
4,03
3,94
4,11
4,17
4,13
4,06
4,12
4,07
4,13
4,13
SCOP 2)
85,00-80,80-77,80 88,10-83,70-80,70 91,30-86,80-83,60 95,40-90,60-87,30 98,30-93,40-90,00 101,70-96,60-93,10 103,50-98,30-94,70 106,80-101,50-97,80
Current
A
Input power
kW
81,20-77,10-74,30 83,30-79,20-76,30 87,40-83,10-80,10 89,20-84,70-81,70 92,30-87,70-84,50 96,90-92,00-88,70 98,30-93,40-90,00 103,40-98,30-94,70
49,70
51,00
54,10
54,60
56,50
59,30
60,80
64,00
Starting current
A
7,00
7,00
7,00
8,00
8,00
8,00
8,00
8,00
External static pressure (Max)
Pa
80
80
80
80
80
80
80
80
Air flow
m³/min
1 266
1 274
1 439
1 274
1 447
1 447
1 620
1 620
66,0 / 63,0
Sound pressure
Normal / Silent mode
dB(A)
66,0 / 63,0
66,5 / 63,5
65,5 / 62,5
66,5 / 63,5
66,5 / 63,5
66,5 / 63,5
66,0 / 63,0
Sound power
Normal mode
dB(A)
87,0
87,5
86,5
87,5
87,5
87,5
87,0
87,0
1 842 x 5 210 x
1 000 / 1 275
1 842 x 5 620 x
1 000 / 1 335
1 842 x 5 570 x
1 000 / 1 335
1 842 x 5 620 x
1 000 / 1 380
1 842 x 5 980 x
1 000 / 1 440
1 842 x 5 980 x
1 000 / 1 440
1 842 x 6 340 x
1 000 / 1 500
1 842 x 6 340 x
1 000 / 1 500
3/4 (19,05) /
7/8 (22,22)
7/8 (22,22) /
1 (25,04)
7/8 (22,22) /
1 (25,04)
7/8 (22,22) /
1 (25,04)
7/8 (22,22) /
1 (25,04)
7/8 (22,22) /
1 (25,04)
7/8 (22,22) /
1 (25,04)
7/8 (22,22) /
1 (25,04)
Dimension /
Net weight
Piping diameter 3)
HxWxD
mm / kg
Liquid
Inch (mm)
Gas
Inch (mm)
Balance
Inch (mm)
1-5/8 (41,28) / 1-5/8 (41,28) / 1-5/8 (41,28) / 1-3/4 (44,45) / 1-3/4 (44,45) / 1-3/4 (44,45) / 1-3/4 (44,45) / 1-3/4 (44,45) /
1-3/4 (44,45) 1-3/4 (44,45) 1-3/4 (44,45)
2 (50,80)
2 (50,80)
2 (50,80)
2 (50,80)
2 (50,80)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
Refrigerant (R410A) / CO2 Eq.
kg / T
32,90 / 68,6952 35,60 / 74,3328 34,10 / 19,836 35,80 / 68,6952 36,80 / 76,8384 36,80 / 76,8384 38,00 / 79,344 38,00 / 79,344
Maximum allowable indoor / outdoor
capacity ratio 4)
%
50 ~ 130 (200)
Operating range
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
Cool Min ~ Max
°C
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
Heat Min ~ Max
°C
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
1) EER and COP calculation is based in accordance to EN14511. 2) SEER / SCOP is calculated based on the seasonal space cooling / heating efficiency “η” values of the COMMISSION REGULATION (EU)
2016/2281. SEER, SCOP = (η + Correction) × PEF. 3) Piping diameter under 90 m for ultimate indoor unit / over 90 m for ultimate indoor unit (if the longest piping equivalent length exceeds 90 m, increase the
sizes of the main tubes by 1 rank for gas tubes and liquid tubes). 4) If the following conditions are satisfied, the effective range is above 130% and below 200%: A. Obey the limited number of connectable indoor
units. B. The lower limit of operating range for heating outdoor temperature is limited to -10 °C WB (standard -25 °C WB). C. Simultaneous operation is limited to less than 130% of connectable indoor units.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
51