UK VRF GEN 24 - Flipbook - Page 48
R410A
GENERAL INDEX
2-Pipe ECOi EX ME2 Series high efficiency model combination from 18 to 64 HP
HP
Outdoor unit
Voltage
Power supply
V
Phase
18 HP
20 HP
22 HP
24 HP
26 HP
28 HP
U-8ME2E8
U-10ME2E8
U-10ME2E8
U-12ME2E8
U-10ME2E8
U-12ME2E8
U-10ME2E8
U-10ME2E8
U-12ME2E8
U-12ME2E8
U-16ME2E8
U-16ME2E8
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
50
50
50
50
50
50
Cooling capacity
kW
50,0
56,0
61,5
68,0
73,0
78,5
EER 1)
W/W
4,55
4,38
4,13
3,93
3,80
3,69
Current
A
Input power
kW
11,00
12,80
14,90
17,30
19,20
Heating capacity
kW
56,0
63,0
69,0
76,5
81,5
87,5
COP 1)
W/W
4,96
4,77
4,76
4,69
4,55
4,56
Frequency
18,20 - 17,30 - 16,60 21,40 - 20,30 - 19,60 24,30 - 23,10 - 22,30 28,00 - 26,60 - 25,60 31,70 - 30,10 - 29,00 34,80 - 33,10 - 31,90
21,30
Current
A
Input power
kW
11,30
13,20
14,50
16,30
17,90
19,20
Starting current
A
2,00
2,00
2,00
2,00
3,00
3,00
External static pressure (Max)
Pa
80
80
80
80
80
80
Air flow
m³/min
448
448
456
464
456
464
Normal
dB(A)
58,5
59,0
61,0
62,0
62,5
63,5
Silent mode
dB(A)
55,5
56,0
58,0
59,0
59,5
60,5
Normal mode
dB(A)
79,5
80,0
82,0
83,0
83,5
84,5
1 842 x 1 600
x 1 000 / 420
1 842 x 2 010
x 1 000 / 480
1 842 x 2 420
x 1 000 / 540
1 842 x 2 010
x 1 000 / 535
1 842 x 2 420
x 1 000 / 585
Sound pressure
Sound power
Dimension /
Net weight
Piping diameter 2)
HxWxD
mm / kg
1 842 x 1 600
x 1 000 / 420
Liquid
Inch (mm)
5/8 (15,88) /
3/4 (19,05)
5/8 (15,88) /
3/4 (19,05)
5/8 (15,88) /
3/4 (19,05)
5/8 (15,88) /
3/4 (19,05)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
Gas
Inch (mm)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/4 (31,75) /
1-1/2 (38,10)
Balance
Inch (mm)
Refrigerant (R410A) / CO2 Eq.
kg / T
Maximum allowable indoor / outdoor
capacity ratio 3)
Operating range
18,70 - 17,70 - 17,10 22,00 - 20,90 - 20,20 23,90 - 22,70 - 21,90 26,60 - 25,30 - 24,40 29,90 - 28,40 - 27,40 31,70 - 30,10 - 29,00
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
11,20 / 23,3856
11,20 / 23,3856
13,90 / 29,0232
16,60 / 34,6608
13,90 / 29,0232
16,60 / 34,6608
%
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
Cool Min ~ Max
°C
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
Heat Min ~ Max
°C
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
HP
Outdoor unit
Voltage
32 HP
34 HP
36 HP
38 HP
40 HP
U-16ME2E8
U-10ME2E8
U-12ME2E8
U-10ME2E8
U-12ME2E8
U-16ME2E8
U-16ME2E8
U-12ME2E8
U-12ME2E8
U-12ME2E8
U-12ME2E8
U-12ME2E8
U-12ME2E8
U-16ME2E8
U-16ME2E8
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
50
50
50
50
50
50
Cooling capacity
kW
85,0
90,0
96,0
101,0
107,0
113,0
EER 1)
W/W
3,68
3,52
4,05
3,95
3,84
3,75
Current
A
Input power
kW
23,10
25,60
23,70
25,60
27,90
30,10
Heating capacity
kW
95,0
100,0
108,0
113,0
119,0
127,0
COP 1)
W/W
4,48
4,42
4,72
4,73
4,61
4,57
Current
A
Input power
kW
21,20
22,60
22,90
23,90
25,80
27,80
Starting current
A
4,00
4,00
3,00
3,00
4,00
4,00
External static pressure (Max)
Pa
80
80
80
80
80
80
Air flow
m³/min
464
464
688
696
688
696
Normal
dB(A)
63,5
64,0
63,0
64,0
64,0
64,5
Silent mode
dB(A)
60,5
61,0
60,0
61,0
61,0
61,5
Normal mode
dB(A)
84,5
85,0
84,0
85,0
85,0
85,5
1 842 x 2 420
x 1 000 / 630
1 842 x 3 250
x 1 000 / 750
1 842 x 3 660
x 1 000 / 810
1 842 x 3 250
x 1 000 / 795
1 842 x 3 660
x 1 000 / 855
Power supply
Phase
Frequency
Sound pressure
Sound power
Dimension /
Net weight
Piping diameter 2)
V
30 HP
U-14ME2E8
35,40 - 33,60 - 32,40 37,70 - 35,80 - 34,60 37,80 - 35,90 - 34,60 39,00 - 37,10 - 35,80 42,60 - 40,50 - 39,00 45,90 - 43,60 - 42,00
HxWxD
mm / kg
1 842 x 2 420
x 1 000 / 630
Liquid
Inch (mm)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
3/4 (19,05) /
7/8 (22,22)
Gas
Inch (mm)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/2 (38,10) /
1-5/8 (41,28)
1-1/2 (38,10) /
1-5/8 (41,28)
1-1/2 (38,10) /
1-5/8 (41,28)
Balance
Inch (mm)
Refrigerant (R410A) / CO2 Eq.
kg / T
Maximum allowable indoor / outdoor
capacity ratio 3)
Operating range
38,60 - 36,60 - 35,30 42,30 - 40,20 - 38,70 38,70 - 36,80 - 35,50 41,40 - 39,30 - 37,90 46,10 - 43,80 - 42,20 49,20 - 46,70 - 45,00
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
16,60 / 34,6608
16,60 / 34,6608
22,20 / 46,3536
24,90 / 51,9912
22,20 / 46,3536
24,90 / 46,3536
%
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
50 ~ 130 (200)
Cool Min ~ Max
°C
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
-10 ~ +52
Heat Min ~ Max
°C
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
-25 ~ +18
Data is for reference. 1) EER and COP calculation is based in accordance to EN14511. 2) Piping diameter under 90 m for ultimate indoor unit / over 90 m for ultimate indoor unit (if the longest piping equivalent
length exceeds 90 m, increase the sizes of the main tubes by 1 rank for gas tubes and liquid tubes). 3) If the following conditions are satisfied, the effective range is above 130% and below 200%: A. Obey the
limited number of connectable indoor units. B. The lower limit of operating range for heating outdoor temperature is limited to -10 °C WB (standard -25 °C WB). C. Simultaneous operation is limited to less than
130% of connectable indoor units.
48