2-Pipe ECOi EX ME2 Series superior flexibility
Maximum allowable connected indoor / outdoor capacity ratio up to 200%*
ECOi EX attain maximum indoor unit connection capacity of up to 130% of the unit's connection range. This limit can be
surpassed and reach up to 200% if some conditions are satisfied. With this feature, ECOi EX provides an ideal air
conditioning solution for locations where full cooling / heating are not always required in all spaces at same time.
System (HP)
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80
Connectable indoor units:
13 16 19 23 26 29 33 36 40 43 46 50 53 56 59
130%
64
Connectable indoor units:
20 25 30 35 40 45 50 55 60
200%
64
Note: If more than 100% indoor units are operated with a high load, the units may not perform at the rated capacity. For the details, please consult with an authorised Panasonic dealer. * If the following
conditions are satisfied, the effective range is above 130% up to 200%. Obey the limited number of connectable indoor units. The lower limit of operating range for heating outdoor temperature is limited to
-10 °C WB (standard -25 °C WB). Simultaneous operation is limited to less than 130% of connectable indoor units. 1,5 kW capacity of Indoor Units are included.
Increased piping lengths and design flexibility
Adaptable to various building types and sizes. Actual
piping length: 200 m. Maximum piping length: 1 000 m.
Up to 50 m length difference between the longest and the
shortest piping from the first branch
Flexible piping layout makes it easier to design systems
for locations such as train stations, airports, schools and
hospitals.
· Up to 64 units can be connected to one system
· Difference between maximum and minimum pipe runs after first branch can be a maximum of
50 m
· Larger pipe runs can be up to 200 m
Maximum height difference between
outdoor unit and indoor unit:
1)
50 m
(Max 90 m) 2)
200m
Maximum height difference
between indoor units:
15 m (Max 30 m)
2)
Farthest pipe length
(from outdoor unit to
farthest indoor unit)
(equivalent length):
200 m
Maximum total pipe length:
1 000 m
L2
L1
L1 = Longest pipe run. L2 = Shortest pipe run. L1 - L2 = Maximum 50 m.
1) 40 m if the outdoor unit is below the indoor unit.
2) For height differences between outdoor unit and indoor unit > 50 m, as well as for height
differences between indoor units > 15 m, contact an authorized Panasonic dealer.
Weight
Required
installation
space.
375 kg
1540 mm
1842 mm
1000 mm
Compact design
The ME2 Series has reduced the installation space required with up to 20 HP available in a single chassis. 8 - 10 HP are
able to fit inside a lift for easy handling on site.
18-20 HP
1000 mm
1800 mm
1640 mm
770 mm