Mini ECOi LZ2 Series 8 and 10 HP · R32
Introducing widest range of R32 Mini VRF.
· SEER levels up to 7,6 and SCOP levels up to 4,6 (for 8 HP model)
· Continuous operation at extreme ambient temperatures: -20 °C (heating) to 52 °C
(cooling)
· Widest range of connectable units in R32 VRF
· Unique indoors with nanoe™ X, hydroxyl radicals contained in water
· Allowing wide range of installations with and without refrigerant mitigation
· Flexible mitigation measures, with Panasonic R32 refrigerant leak detector / alarm
to be installed only when required
HP
8 HP
10 HP
U-8LZ2E8
U-10LZ2E8
380 - 400-415
380 - 400 - 415
Three phase
Three phase
Outdoor unit
Voltage
Power supply
V
Phase
Frequency
Cooling capacity
Industry 1st
8 HP and 10 HP
Mini VRF units
with R32
Hz
50
50
kW
22,4
28,0
EER 1)
W/W
Current
A
3,84
3,47
9,73 - 9,25 - 8,91
13,2 - 12,5 - 12,1
Input power
Heating capacity
kW
5,83
8,07
kW
25,0
28,0
COP 1)
W/W
4,30
4,47
Current
A
9,81 - 9,32 - 8,98
10,5 - 9,93 - 9,57
Input power
kW
5,81
6,26
Starting current
A
1,0
1,0
Maximum current
A
13,7
19,5
Maximum input power
kW
8,21 - 8,64 - 8,96
11,9 - 12,6 - 13,0
Maximum number of connectable indoor units 2)
External static pressure
Pa
Air flow
Sound pressure
16
16
0 ~ 35
0 ~ 35
m³/min
158
167
Cool
dB(A)
59,0
60,0
57 / 55 / 53 / 50
Cool (Silent 1 / 2 / 3 / 4)
dB(A)
56 / 54 / 52 / 50
Sound power
Cool
dB(A)
72
74
Dimension
HxWxD
mm
1 500 x 980 x 370
1 500 x 980 x 370
Net weight
kg
Piping diameter
125
126
Liquid
Inch (mm)
3/8 (9,52)
3/8 (9,52)
Gas
Inch (mm)
3/4 (19,05)
7/8 (22,22)
Maximum piping length (total)
m
100 (300)
100 (300)
Elevation difference (in / out)
m
50 (OU above) / 40 (OU below)
50 (OU above) / 40 (OU below)
Refrigerant (R32)
kg
4,9
5,1
Maximum allowable indoor / outdoor capacity ratio 3)
%
50 ~ 150 (130)
50 ~ 150 (130)
Cool Min ~ Max
°C
-10 ~ 52
-10 ~ 52
Heat Min ~ Max
°C
-20 ~ 18
-20 ~ 18
Operating range
ErP data 4)
SEER 5)
ηs,c
7,56
7,08
299,4%
280,2%
SCOP 5)
ηs,h
4,59
4,60
180,6%
181,0%
1) EER and COP calculation is based on EN 14511. 2) The number in parenthesis indicates maximum number of connectable indoor unit in case of 1,5 kW indoor units connection. 3) The number in parenthesis
indicates maximum allowed indoor / outdoor capacity ratio in case of 1,5 kW indoor units connection. 4) SEER / SCOP and ηs,c / ηs,h are in accordance with ErP test data for F2 type variable static pressure hideaway indoor units. 5) SEER / SCOP is calculated based on the seasonal space cooling / heating efficiency “η” values of the COMMISSION REGULATION (EU) 2016/2281. SEER, SCOP = (η + Correction) × PEF.
Perfect fit for small to medium size projects
8 and 10 HP LZ2 Mini VRF units bring in the total benefits
of a VRF system in a smaller application. You can enjoy
advanced individual and central VRF control options
including the revolutionary Panasonic AC Smart Cloud and
AC Service Cloud.
R32
R2 ROTARY
COMPRESSOR
BLUEFIN
-10 °C
-20 °C
COOLING MODE
HEATING MODE
AUTOMATIC
RESTART
PANASONIC
AC SMART CLOUD
For the most difficult conditions
The Mini ECOi LZ2 series are able to operate at the
hardest conditions from -20 °C up to +52 °C providing
continuous and efficient, heating and cooling for your
space all year long.
OPTIONAL WI-FI
INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.