GENERAL INDEX
Mini ECOi LZ2 Series 4 to 6 HP · R32
Outstanding efficiency in a compact body and continuous operation even at
extreme ambient temperatures.
· SEER levels up to 8,5 and SCOP levels up to 5,0 (for 4 HP model)
· Continuous operation at extreme ambient temperatures: -20 °C (heating) to 52 °C
(cooling)
· Wide range of connectable units
· Unique indoors with nanoe™ X, hydroxyl radicals contained in water
· Allowing wide range of installations with and without mitigation measures
· Flexible mitigation measures, with Panasonic R32 refrigerant leak detector / alarm
to be installed only when required
HP
Low height
996 mm
4 HP
5 HP
6 HP
4 HP
5 HP
6 HP
U-4LZ2E5
U-5LZ2E5
U-6LZ2E5
U-4LZ2E8
U-5LZ2E8
U-6LZ2E8
220 - 230 - 240
220 - 230 - 240
220 - 230 - 240
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
Single phase
Single phase
Single phase
Three phase
Three phase
Three phase
Hz
50
50
50
50
50
50
Cooling capacity
kW
12,1
14,0
15,5
12,1
14,0
15,5
EER 1)
W/W
4,53
4,12
3,88
Current
A
Input power
kW
2,67
3,40
Heating capacity
kW
12,5
16,0
COP 1)
W/W
5,27
4,71
Outdoor unit
Voltage
Power supply
V
Phase
Frequency
4,53
4,12
3,88
4,37 - 4,15 - 4,00
5,50 - 5,23 - 5,04
6,44 - 6,12 - 5,89
4,00
2,67
3,40
4,00
16,5
12,5
16,0
16,5
4,42
5,27
4,71
4,42
13,30 - 12,80 - 12,20 16,90 - 16,20 - 15,50 19,60 - 18,70 - 18,00
Current
A
3,91 - 3,71 - 3,58
5,50 - 5,22 - 5,03
6,02 - 5,72 - 5,51
Input power
kW
12,00 - 11,40 - 11,00 16,90 - 16,20 - 15,50 18,50 - 17,70 - 17,00
2,37
3,40
3,73
2,37
3,40
3,73
Starting current
A
1,0
1,0
1,0
1,0
1,0
1,0
Maximum current
A
19,6
23,7
26,5
7,2
9,2
9,9
Maximum input power
kW
3,92 - 4,10 - 4,28
4,76 - 4,98 - 5,19
5,41 - 5,66 - 5,90
4,40 - 4,63 - 4,80
5,69 - 5,99 - 6,22
6,15 - 6,47 - 6,72
Maximum number of connectable indoor units 2)
7 (10)
8 (12)
9 (12)
7 (10)
8 (12)
9 (12)
External static pressure
0 ~ 35
0 ~ 35
0 ~ 35
0 ~ 35
0 ~ 35
0 ~ 35
Pa
Air flow
Cool
Sound pressure
m³/min
69
72
74
69
72
74
dB(A)
52
53
54
52
53
54
51 / 49 / 47 / 45
Cool (Silent 1 / 2 / 3 / 4) dB(A)
49 / 47 / 45 / 45
50 / 48 / 46 / 45
51 / 49 / 47 / 45
49 / 47 / 45 / 45
50 / 48 / 46 / 45
Heat
dB(A)
54
56
56
54
56
56
Sound power
Cool / Heat
dB(A)
69 / 72
70 / 74
72 / 75
69 / 72
70 / 74
72 / 75
Dimension
HxWxD
mm
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
94
94
94
94
94
94
Net weight
Piping diameter
kg
Liquid
Inch (mm)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
Gas
Inch (mm)
5/8 (15,88)
Maximum piping length (total)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
m
90 (180)
90 (180)
90 (180)
90 (180)
90 (180)
90 (180)
50 (OU above) /
40 (OU below)
50 (OU above) /
40 (OU below)
50 (OU above) /
40 (OU below)
50 (OU above) /
40 (OU below)
50 (OU above) /
40 (OU below)
Elevation difference (in / out)
m
50 (OU above) /
40 (OU below)
Refrigerant (R32)
kg
2,7
2,7
2,7
2,7
2,7
2,7
Maximum allowable indoor / outdoor
capacity ratio 3)
%
50 ~ 150 (130)
50 ~ 150 (130)
50 ~ 150 (130)
50 ~ 150 (130)
50 ~ 150 (130)
50 ~ 150 (130)
Cool Min ~ Max
°C
-10 ~ 52
-10 ~ 52
-10 ~ 52
-10 ~ 52
-10 ~ 52
-10 ~ 52
Heat Min ~ Max
°C
-20 ~ 18
-20 ~ 18
-20 ~ 18
-20 ~ 18
-20 ~ 18
-20 ~ 18
Operating range
ErP data 4)
SEER 5)
ηs,c
8,50
8,12
7,71
8,50
8,12
7,71
337,0%
321,8%
305,4%
337,0%
321,8%
305,4%
SCOP 5)
ηs,h
5,05
4,61
4,59
5,05
4,61
4,59
199,0%
181,4%
180,6%
199,0%
181,4%
180,6%
1) EER and COP calculation is based on EN 14511. 2) The number in parenthesis indicates maximum number of connectable indoor unit in case of 1,5 kW indoor units connection. 3) The number in parenthesis
indicates maximum allowed indoor / outdoor capacity ratio in case of 1,5 kW indoor units connection. 4) SEER / SCOP and ηs,c / ηs,h are in accordance with ErP test data for U2 type 4 way 90x90 cassette indoor
units. 5) SEER / SCOP is calculated based on the seasonal space cooling / heating efficiency “η” values of the COMMISSION REGULATION (EU) 2016/2281. SEER, SCOP = (η + Correction) × PEF.
Minimum environmental impact
Panasonic has designed the LZ2 series in order to
minimize the environmental impact of the system. Low
GWP refrigerant R32 and highest efficiency levels ensure
this through the total operational lifetime.
R32
R2 ROTARY
COMPRESSOR
INTERNET CONTROL: Optional.
28
BLUEFIN
-10 °C
-20 °C
COOLING MODE
HEATING MODE
AUTOMATIC
RESTART
For the most challenging spaces
The Mini ECOi LZ2 R32 VRF system is the ideal solution to