Outdoor unit capacity
4 HP
4 HP
5 HP
8 HP
Air outlet height 2,7 m
PAW-10EAIRC-LS
PAW-15EAIRC-LS
PAW-20EAIRC-LS
PAW-25EAIRC-LS
17,0
Cooling capacity 1)
Max
kW
6,1
9,7
13,0
Heating capacity 2)
Max
kW
7,9
12,0
15,0
19,0
Air flow
High
m³/h
1 800
2 700
3 600
4 500
Heat Exchanger
Volume
L
1,67
2,85
3,94
5,03
Electric consumption fan
230 V / 50 Hz
kW
0,30
0,50
0,60
0,80
Current
230 V / 50 Hz
A
2,10
3,10
4,10
5,10
Sound pressure 3)
Max
dB(A)
65
66
67
69
PAW-10EAIRC-HS
PAW-15EAIRC-HS
PAW-20EAIRC-HS
PAW-25EAIRC-HS
23,7
Air outlet height 3,0 m
Cooling capacity 1)
Max
kW
9,1
13,0
19,5
Heating capacity 2)
Max
kW
11,8
15,8
23,6
27,6
Air flow
High
m³/h
2 700
3 600
5 400
6 300
Heat Exchanger
Volume
L
1,67
2,85
3,94
5,12
Electric consumption fan
230 V / 50 Hz
kW
0,75
1,00
1,50
1,75
Current
230 V / 50 Hz
A
4,10
5,50
8,20
9,60
Sound pressure 3)
Max
dB(A)
66
67
68
68
HxWxD
mm
260 (+140) x 2 500 x 460
Common data
Dimension 4)
Net weight
260 (+140) x 1 000 x 460
260 (+140) x 1 500 x 460
260 (+140) x 2 000 x 460
Air outlet height 2,7 m kg
50
65
80
95
Air outlet height 3,0 m kg
55
65
85
110
Fan type
Piping diameter
Liquid / Gas
Inch (mm)
Door width
EC
EC
EC
EC
3/8 (9,52) / 5/8 (15,88)
3/8 (9,52) / 3/4 (19,05)
3/8 (9,52) / 7/8 (22,22)
3/8 (9,52) / 7/8 (22,22)
m
Refrigerant
1,0
1,5
2,0
2,5
R32 / R410A
R32 / R410A
R32 / R410A
R32 / R410A
LS / VRF outdoor combination
HS / VRF outdoor combination
Operation until
40 °C
35 °C
30 °C
Operation until
40 °C
35 °C
30 °C
PAW-1EAIRC-LS
U-4
U-4
U-4
PAW-10EAIRC-HS
U-6
U-5
U-4
PAW-15EAIRC-LS
U-6
U-5
U-4
PAW-15EAIRC-HS
U-8
U-6
U-4
PAW-20EAIRC-LS
U-8
U-6
U-4
PAW-20EAIRC-HS
U-8
U-8
U-8
PAW-25EAIRC-LS
U-8
U-8
U-5
PAW-25EAIRC-HS
U-12
U-10
U-8
1) Cooling capacity DX coil, air temperature in / out +27 / +18 °C, R32 and R410. 2) Heating capacity condenser, air temperature in / out +20 / +33 °C, R32 and R410. In the case of lower outdoor temperatures, an
outdoor model with higher capacity may be necessary. 3) Measured in distance up to 5,0 m, direction factor 2, absorbing surfaces 200 m², Min / Max air flow. 4) 140 mm is the height of an electrical box if it is
installed on the top. * Also compatible with ECO G Series (GE3 and GF3) and Hybrid Serie.
Technical focus
· Compatible with R32 and R410A refrigerant
· Save up to 40% energy costs by use of the integrated EC
fan technology (higher efficiency than conventional AC
fan, soft start and longer motor duration)
· 4 length of air curtain LS and HS are available 1,0, 1,5,
2,0 and 2,5 m
· Installation height up to 3,0 m
· Outlet grilles can be adjusted in five positions, to suite
different indoor and installation requirements
· Control with Panasonic remote control systems (optional)
· Direct integration to BMS via optional Panasonic
interfaces
· Drip tray included in all DX air curtains
· Drain pump included
Internet control
An app added to your tablet or smartphone or via the
Internet allows you to control and manage the system
remotely. There is also the option to integrate into existing
BMS systems by using other Panasonic interfaces.
BMS
CONNECTIVITY
102
Rating Conditions: Cooling Outdoor +35 °C DB Indoor +27 °C DB / +19 °C WB, Discharge temperature 16 °C. All combinations under rated conditions: Heating Outdoor +7 °C DB/+6 °C WB Indoor +20 °C DB. In case of lower outdoor temperatures a higher