UK CLOSE CONTROL GEN 24 - Flipbook - Page 6
CLOSE CONTROL / VERTICAL DX UNITS
GENERAL INDEX
P Series - Perimetral
Perimetral and compact solution.
Cooling capacity - chilled water: 9,9 to 160,0 kW.
Cooling capacity - direct expansion: 8,2 to 95,0 kW.
The range at a glance
Although optimised for data centres, the technical
characteristics of the P Series units make them ideal for
various types of special applications, including: metrology
labs, TV production studios, musical instrument recording
and storage rooms, museums and archives, control rooms
in power stations and railway junctions.
Moreover, they are ideal for use in many industrial
sectors: optics, electronics, electromedical devices,
electrical or electronic equipment production, musical
instrument production, etc.
Advantages
· Versions with upward and downward air delivery
· Strict control of room temperature and humidity
· Very high EER (energy efficiency ratio) and low operating
costs
· High usage flexibility and wide range of accessories
Free cooling and two sources models available.
Technical features
UPA/OPA - direct expansion air conditioners with air-cooled or water-cooled condensers
Sizes
Cooling capacity 1)
kW
Sensible cooling capacity 1)
kW
EER 2)
71
141
211
251
301
321
322
361
461
422
512
662
852
932
8,2
14,7
21,0
27,4
32,3
35,2
33,8
38,1
48,1
43,7
57,8
67,3
84,4
94,9
7,9
12,9
21,0
25,7
32,3
35,2
33,8
38,1
46,8
43,7
53,6
66,2
73,7
86,3
3,83
3,40
3,30
3,14
3,21
3,13
3,34
3,57
3,63
3,47
3,34
3,26
3,27
3,64
21 000
Air flow rate
m³/h
2 200
3 200
7 000
7 000
12 000
12 000
12 000
14 000
14 000
14 000
14 000
18 000
18 000
Sound pressure level 3)
dB(A)
51
59
56
57
67
67
67
58
58
58
59
61
61
61
Height
mm
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
Width
mm
750
750
860
860
1 410
1 410
1 410
1 750
1 750
1 750
1 750
2 300
2 300
2 640
Depth
mm
600
600
880
880
880
880
880
880
880
880
880
880
880
880
kg
170
225
280
305
360
385
430
460
470
535
540
685
705
745
Air-cooled free cooling
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Water-cooled free cooling
○
○
○
○
○
●
○
○
●
○
○
●
●
○
Two sources
○
○
●
○
○
●
○
○
●
○
●
●
●
●
Dimension
Overall weight
UPU/OPU - chilled water air conditioners
Sizes
Cooling capacity 1)
kW
Sensible cooling capacity 1)
kW
EER 2)
10
20
30
50
60
70
80
110
160
220
9,9
17,2
30,0
41,0
52,8
63,1
65,4
80,0
110,0
160,0
9,3
14,9
27,8
36,2
47,4
54,2
61,8
73,0
99,7
146,0
38,26
29,13
30,00
24,54
22,75
24,17
24,79
24,17
29,33
24,17
36 000
Air flow rate
m³/h
2 200
3 200
7 000
8 000
12 000
12 000
16 000
18 000
24.000
Sound pressure level 3)
dB(A)
51
59
56
60
67
68
61
62
62
65
Dimension
Overall weight
Two sources
Height
mm
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
1 990
Width
mm
750
750
860
860
1 410
1 410
1 750
1 750
2 640
3 495
Depth
mm
600
600
880
880
880
880
880
880
880
880
kg
125
150
245
250
270
280
375
410
690
810
○
○
○
●
○
●
○
●
●
○
1) Performance refers to: intake air 24 °C-45%Rh; R410A refrigerant; condensing temperature 45 °C; water temperature 7/12 °C; external static pressure 30 Pa. The declared performance does not consider the
heat generated by the fans, which must be added to the thermal load of the system. 2) EER (energy efficiency ratio) = total cooling capacity / input power of compressors + input power of fans (excluding aircooled condensers). 3) Sound pressure levels at a distance of 2 m; in a free field; pursuant to UNI EN ISO 3744:2010.
6