UK CLOSE CONTROL GEN 24 - Flipbook - Page 13
CLOSE CONTROL / VERTICALCHILLERS
DX UNITS
CLOSE CONTROL / VERTICAL DX INDEX
Technical features
Size
1 200
1 900
2 450
3 250
4 650
T-X1200.AO
T-X1900.AO
T-X2450.AO
T-X3250.AO
T-X4650.AO
W
15 005
18 000
23 000
32 400
45 700
BTU/hr
51 200
61 400
78 500
110 550
157 200
T-XAO - water cooled models
Cooling capacity 1)
Nominal
Nominal treated air
m³/h
2 000
3 200
4 500
5 800
9 000
Min / Max treated air
m³/h
1 500 / 2 500
2 500 / 3 800
3 600 / 5 400
4 600 / 7 000
7 200 / 10 800
Nominal fresh air (with accessory)
Static pressure 2)
m³/h
180
285
420
500
1 300
Standard unit
daPa
0 / 13
0 / 21
0 / 20
0 / 25
0 / 23
Sound pressure 3)
Normal speed
dB(A)
51
55
58
64
60
Voltage
V
Air flow
Electrical data
Power supply
Phase
Frequency
Voltage range
Hz
V
Total input power 1)
Input power ventilation
Min / Max - standard unit
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
50
50
50
50
50
360 / 440
360 / 440
360 / 440
360 / 440
360 / 440
W
4 843
6 616
7 100
9 800
13 900
W
260 / 510
380 / 580
500 / 1 100
700 / 1 800
1 600 / 2 400
2 800
Water circuit 1)
Wasted water - flow
L/h
914
950
1 000
1 700
Wasted water - pressure drop
kPa
37
30
22
35
18
Recycled water - flow
L/h
3 161
3 050
3 500
5 780
8 300
Recycled water - pressure drop
kPa
80
65
45
40
56
mm
1 540
1 735
1 840
1 830
1 970
mm
430
500
600
600
790
mm
890
1 000
1 300
1 530
1 715
Dimensions
Dimensions
HxWxL
T-CX - water cooled models
CX25
W
8 000
BTU/hr
27 300
Nominal treated air
m³/h
1 500
Motor input power
W
245
Voltage
V
Nominal cooling capacity (W 18 °C, A 19 °C Wet Bulb)
Air flow
Electrical data
Power supply
Phase
230
400
Single phase
Three phase
Frequency
Hz
50
50
Nominal
A
12,28
5,28
Max
A
14,85
6,38
aM fuse
A
16
8
ASE/VDE fuse
A
16
10
Nominal
A
26
9,6
Max
A
31
11,61
aM fuse
A
32
12
ASE/VDE fuse
A
35
16
Cooling + ventilation
Input
Electric heater + ventilation
Input
Dimensions
Dimensions
HxWxL
mm
1 280
mm
407
mm
800
1) International standard ISO 51.51 conditions. 27 °C/19 °C (WB) - outside air : 35 °C/24 °C (WB). Wasted water: inlet +15 °C - recycled water inlet/outlet: 30 °C/35 °C. 2) Pressure in air flow range at nominal
voltage, without accessories. 3) Total sound pressure dB(A) (4 m) under nominal conditions in a room of 1 000 m³ (reverberation 0,83 s).
Accessories and options
Accessories and options
Air distribution duct frame
Hot water coil
Electric heaters
ON / OFF switch and room thermostat
Fresh air intake
Remote fault reporting
Front air distribution plenum
Sump heating resistance
High ventilation (provided as standard for CX25, X1200.AO and X1900.AO)
Total rear intake duct frame
COAXIAL HEAT
EXCHANGER
SCROLL
COMPRESSOR
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.