UK BIGRAC GEN 24 - Flipbook - Page 64
GENERAL INDEX
Air curtain with DX coil, connected to PACi NX and PACi
Comfort: Easy redirection of air flow by means of manual deflector.
Ease of use: Speed selector (high and low) on the unit itself.
Easy installation and maintenance: Easy installation / Compact dimensions
improve installation and positioning / Easy cleaning of grid without opening of
the unit.
Outdoor unit capacity
7,1 kW
10,0 kW
14,0 kW
20,0 kW
Air outlet height 2,7 m
PAW-10PAIRC-LS-1
PAW-15PAIRC-LS-1
PAW-20PAIRC-LS-1
PAW-25PAIRC-LS-1
17,0
Cooling capacity 1)
Max
kW
6,1
9,7
13,0
Heating capacity 2)
Max
kW
7,9
12,0
15,0
19,0
Air flow
High
m³/h
1 800
2 700
3 600
4 500
Heat Exchanger
Volume
L
1,67
2,85
3,94
5,03
Electric consumption fan
230 V / 50 Hz
kW
0,30
0,50
0,60
0,80
Current
230 V / 50 Hz
A
2,10
3,10
4,10
5,10
Sound pressure 3)
Max
dB(A)
65
66
67
69
PAW-10PAIRC-HS-1
PAW-15PAIRC-HS-1
PAW-20PAIRC-HS-1
PAW-25PAIRC-HS-1
23,7
Air outlet height 3,0 m
Cooling capacity 1)
Max
kW
9,1
13,0
19,5
Heating capacity 2)
Max
kW
11,8
15,8
23,6
27,6
Air flow
High
m³/h
2 700
3 600
5 400
6 300
Heat Exchanger
Volume
L
1,67
2,85
3,94
5,12
Electric consumption fan
230 V / 50 Hz
kW
0,75
1,00
1,50
1,75
Current
230 V / 50 Hz
A
4,10
5,50
8,20
9,60
Sound pressure 3)
Max
dB(A)
66
67
68
68
HxWxD
mm
260 (+140) x 2 500 x 460
Common data
Dimension 4)
Net weight
260 (+140) x 1 000 x 460
260 (+140) x 1 500 x 460
260 (+140) x 2 000 x 460
Air outlet height 2,7 m kg
50
65
80
95
Air outlet height 3,0 m kg
55
65
85
110
Fan type
Piping diameter
Liquid / Gas
Door width
Inch (mm)
EC
EC
EC
EC
3/8 (9,52) / 5/8 (15,88)
3/8 (9,52) / 3/4 (19,05)
3/8 (9,52) / 7/8 (22,22)
3/8 (9,52) / 7/8 (22,22)
m
Refrigerant
LS / PACi outdoor combination*
PACi Elite
1,0
1,5
2,0
2,5
R32
R32
R32
R32
PACi Standard
HS / PACi outdoor combination*
PACi Elite
PACi Standard
Operation until
40 °C
35 °C
30 °C
40 °C
35 °C
30 °C
Operation until
40 °C
35 °C
30 °C
40 °C
35 °C
30 °C
PAW-10PAIRC-LS-1
U-100
U-100
U-50
U-100
U-100
U-60
PAW-10PAIRC-HS-1
U-200
U-100
U-100
—
U-100
U-100
PAW-15PAIRC-LS-1
U-200
U-100
U-100
—
U-100
U-100
PAW-15PAIRC-HS-1
U-200
U-200
U-100
—
U-200
U-100
PAW-20PAIRC-LS-1
U-200
U-140
U-100
—
—
U-100
PAW-20PAIRC-HS-1
—
U-250
U-200
—
U-250
—
PAW-25PAIRC-LS-1
U-250
U-200
U-125
—
—
U-125
PAW-25PAIRC-HS-1
—
U-250
U-200
—
U-250
—
1) Cooling capacity DX coil, air temperature in / out +27 / +18 °C, R32 and R410. 2) Heating capacity condenser, air temperature in / out +20 / +33 °C, R32 and R410. In the case of lower outdoor temperatures, an
outdoor model with higher capacity may be necessary. 3) Measured in distance up to 5,0 m, direction factor 2, absorbing surfaces 200 m², Min / Max air flow. 4) 140 mm is the height of an electrical box if it is
installed on the top. * Available with PZH2 and PZ2. PZH3 and PZ3 will be compatible from Spring 2024.
Technical focus
· Now compatible with PACi NX Series
· Save up to 40% energy costs by use of the integrated EC
fan technology (higher efficiency than conventional AC
fan, soft start and longer motor duration)
· 4 length of air curtain LS and HS are available 1,0, 1,5,
2,0 and 2,5 m
· Installation height up to 3,0 m
· Outlet grilles can be adjusted in five positions, to suite
different indoor and installation requirements
· Control with Panasonic remote control systems (optional)
· Direct integration to BMS via optional Panasonic
interfaces
· Drip tray included in all DX air curtains
· Drain pump included
How does it work?
Stale air from the room is taken in and ejected near the
door. This creates a ‘roll of air’ that shields the door area,
mixing with the colder incoming air. It then turns away
from the door, back into the room and toward the intake
screen, where it is partly drawn in again. This flow of air
helps to create a barrier for heat loss yet at the same time
refreshes room air
Maximum installation high:
HS: 3,0 m
LS: 2,7 m
BMS
CONNECTIVITY
64
Rating Conditions: Cooling Outdoor +35 °C DB Indoor +27 °C DB / +19 °C WB, Discharge temperature 16 °C. All combinations under rated conditions: Heating Outdoor +7 °C DB/+6 °C WB Indoor +20 °C DB. In case of lower outdoor temperatures a higher
capacity outdoor unit model may be necessary. Specifications subject to change without notice. For detailed information about ErP, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.