UK BIGRAC GEN 24 - Flipbook - Page 54
R32
GENERAL INDEX
Commercial twin, triple and
double-twin systems · R32
New
2023
PACi NX Elite and PACi Elite outdoor units · R32
PACi NX
7,1 kW
10,0 kW
Big PACi NX
12,5 kW
14,0 kW
Big PACi
20,0 kW
25,0 kW
20,0 kW
25,0 kW
—
—
—
—
Outdoor unit single phase
U-71PZH4E5
U-100PZH4E5 U-125PZH4E5 U-140PZH4E5
Outdoor unit three phase
U-71PZH4E8
U-100PZH4E8 U-125PZH4E8 U-140PZH4E8 U-200PZH4E8 U-250PZH4E8 U-200PZH2E8 U-250PZH2E8
Cooling capacity 1)
Nominal (Min - Max) kW
7,1 (2,2 - 9,0)
9,5 (3,1 - 12,5)
Heating capacity 1)
Nominal (Min - Max) kW
8,0 (2,0 - 9,0)
11,2 (3,1 - 14,0) 14,0 (3,2 - 16,0) 16,0 (3,3 - 18,0) 22,4 (5,0 - 24,5) 24,0 (5,5 - 27,6) 22,4 (5,0 - 25,0) 28,0 (5,5 - 31,5)
Power supply
12,5 (3,2 - 14,0) 13,4 (3,3 - 16,0) 19,0 (5,7 - 20,0) 22,0 (6,1 - 25,6) 20,0 (5,7 - 22,4) 25,0 (6,1 - 28,0)
Single phase
V
220 - 230 - 240 220 - 230 - 240 220 - 230 - 240 220 - 230 - 240
Three phase
V
380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415 380 - 400 - 415
—
—
—
—
Connection indoor / outdoor
mm²
Air flow
Cool / Heat
m³/min
Sound pressure
Cool / Heat (Hi)
Sound power
Cool / Heat (Hi)
Dimension
HxWxD
mm
Net weight
1ph / 3ph
kg
66
84 / 82
86 / 84
86 / 84
190
190
117
128
Liquid
Inch (mm)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
1/2 (12,70)
1/2 (12,70)
3/8 (9,52)
1/2 (12,70)
Gas
Inch (mm)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
7/8 (22,22)
7/8 (22,22)
1 (25,40)
1 (25,40)
Min ~ Max
m
5 ~ 60
5 ~ 100
5 ~ 100
5 ~ 100
5 ~ 100
5 ~ 100
5 ~ 90
5 ~ 60
Elevation difference
Max
(in / out)
m
15 / 30 2)
15 / 30 2)
15 / 30 2)
15 / 30 2)
30
30
30
30
Pre-charged pipe length
m
30
30
30
30
30
30
30
30
Additional gas amount
g/m
30
40
40
40
80
80
60
80
Refrigerant (R32) / CO2 Eq.
kg / T
1,95 / 1,32
2,70 / 1,82
3,00 / 2,03
3,00 / 2,03
4,80 / 3,24
4,80 / 3,24
4,20 / 2,835
5,20 / 3,51
Cool Min ~ Max
°C
-15 ~ +52
-20 3) ~ +52
-20 3) ~ +52
-20 3) ~ +52
-15 ~ +52
-15 ~ +52
-15 ~ +46
-15 ~ +46
Heat Min ~ Max
°C
-20 ~ +24
-20 ~ +24
-20 ~ +24
-20 ~ +24
-20 ~ +35
-20 ~ +35
-20 ~ +24
-20 ~ +24
Piping diameter
Pipe length range
Operating range
2x1,5 or 2,5
2x1,5 or 2,5
2x1,5 or 2,5
2x1,5 or 2,5
—
—
—
—
62,0 / 66,0
76,0 / 70,0
86,0 / 78,0
89,0 / 83,0
164 / 164
160 / 160
164 / 164
160 / 160
dB(A)
48 / 50
52 / 52
55 / 55
56 / 56
59 / 61
59 / 63
59 / 61
59 / 63
dB(A)
65 / 67
69 / 69
73 / 73
74 / 74
77 / 79
78 / 82
77 / 79
78 / 82
996 x 980 x 370 996 x 980 x 370 996 x 980 x 370 996 x 980 x 370 996x1140x460 996x1140x460 1500x980x370 1500x980x370
1) 7,1 - 14,0 kW with 4 way 90x90 cassette. 20,0 - 25,0 kW with high static pressure hide-away. 2) Outdoor unit located lower / outdoor unit located higher. 3) Pipe length up to 30 m.
PACi NX Standard outdoor units · R32
10,0 kW
12,5 kW
14,0 kW
Outdoor unit single phase
U-100PZ3E5
U-125PZ3E5
U-140PZ3E5
Outdoor unit three phase
U-100PZ3E8
U-125PZ3E8
U-140PZ3E8
Cooling capacity 1)
Nominal (Min - Max)
kW
10,0 (3,0 - 11,5)
12,5 (3,2 - 13,5)
14,0 (3,3 - 15,0)
Heating capacity 1)
Nominal (Min - Max)
kW
10,0 (3,0 - 14,0)
12,5 (3,3 - 15,0)
14,0 (3,4 - 16,0)
Single phase
V
220-230-240
220-230-240
220-230-240
Three phase
V
380 - 400 - 415
380 - 400 - 415
380 - 400 - 415
2x1,5 or 2,5
2x1,5 or 2,5
2x1,5 or 2,5
73,0 / 73,0
82,0 / 80,0
84,0 / 82,0
Power supply
Connection indoor / outdoor
mm²
Air flow
Cool / Heat
m³/min
Sound pressure
Cool / Heat (Hi)
dB(A)
52 / 52
55 / 55
56 / 56
Sound power
Cool / Heat (Hi)
dB(A)
70 / 70
73 / 73
74 / 74
Dimension
HxWxD
996 x 980 x 370
996 x 980 x 370
996 x 980 x 370
83
87
87
Net weight
Piping diameter
mm
kg
Liquid
Inch (mm)
3/8 (9,52)
3/8 (9,52)
3/8 (9,52)
5/8 (15,88)
Gas
Inch (mm)
5/8 (15,88)
5/8 (15,88)
Pipe length range
Min ~ Max
m
5 ~ 50
5 ~ 50
5 ~ 50
Elevation difference (in / out) 2)
Max
m
15 / 30
15 / 30
15 / 30
Pre-charged pipe length
m
30
30
30
Additional gas amount
g/m
45
45
45
Refrigerant (R32) / CO2 Eq.
kg / T
2,4 / 1,62
2,8 / 1,89
2,8 / 1,89
Cool Min ~ Max
°C
-10 ~ +43
-10 ~ +43
-10 ~ +43
Heat Min ~ Max
°C
-15 ~ 24
-15 ~ 24
-15 ~ 24
Operating range
1) With 4 way 90x90 cassette. 2) Outdoor unit located lower / outdoor unit located higher.
54