UK BIGRAC GEN 24 - Flipbook - Page 51
R32
COMMERCIAL INDEX
COMMERCIAL
Big PACi high static pressure hide-away 20,0-25,0 kW · R32
COMPATIBLE WITH ALL PANASONIC CONNECTIVITY SOLUTIONS. FOR
DETAILED INFORMATION GO TO THE CONTROL SYSTEMS SECTION
Optional:
Infrared
remote
controller.
CZ-RWS3 +
CZ-RWRC3
CONEX wired
remote
controller,
black.
CZ-RTC6/BL
CONEX wired
remote
controller,
white.
CZ-RTC6W/BL
Econavi
sensor.
CZ-CENSC1
CZ-RTC5B
Three phase
Kit
20,0 kW
25,0 kW
KIT-200PE3ZH8
KIT-250PE3ZH8
Remote controller
CZ-RTC5B
CZ-RTC5B
Cooling capacity
Nominal (Min - Max)
kW
19,5 (5,7 - 21,0)
23,2 (6,1 - 27,0)
EER 1)
Nominal (Min - Max)
W/W
3,22 (3,09 - 4,52)
3,11 (2,93 - 4,59)
207,0%
190,6%
SEER / ηs,c 2)
Pdesign
kW
19,5
23,2
6,06 (1,26 - 6,80)
7,46 (1,33 - 9,20)
Input power
Nominal (Min - Max)
kW
Heating capacity
Nominal (Min - Max)
kW
22,4 (5,0 - 25,0)
28,0 (5,5 - 29,0)
COP 1)
Nominal (Min - Max)
W/W
3,61 (3,16 - 4,76)
3,41 (3,05 - 5,00)
141,3%
142,7%
SCOP / ηs,h 2)
Pdesign at -10 °C
Input power
Nominal (Min - Max)
kW
17,0
20,0
kW
6,21 (1,05 - 7,90)
8,21 (1,10 - 9,50)
Indoor unit
Power supply
V / ph / Hz
S-200PE3E5B
S-250PE3E5B
220 - 230 - 240 / 1 / 50
220 - 230 - 240 / 1 / 50
External static pressure at shipment (adjustable)
Pa
75 3) (120 / 180)
75 3) (130 / 200)
Air flow
Hi / Med / Lo
m³/min
72 / 63 / 53
84 / 72 / 59
Sound pressure 4)
Hi / Med / Lo
dB(A)
46 / 44 / 41
47 / 45 / 42
Dimension / Net weight
HxWxD
mm / kg
486 x 1 456 x 916 / 86
486 x 1 456 x 916 / 88
U-200PZH2E8
U-250PZH2E8
V / ph / Hz
380 - 400 - 415 / 3 / 50
380 - 400 - 415 / 3 / 50
Outdoor unit
Power supply
Recommended fuse
A
Air flow
30
30
164 / 164
160 / 160
dB(A)
59 / 61
59 / 63
dB(A)
77 / 79
78 / 82
1 500 x 980 x 370 / 117
1 500 x 980 x 370 / 128
3/8 (9,52) / 1 (25,40)
1/2 (12,70) / 1 (25,40)
5 ~ 90 / 30
5 ~ 60 / 30
Cool / Heat
m³/min
Sound pressure
Cool / Heat (Hi)
Sound power
Cool / Heat (Hi)
Dimension 5) / Net weight
HxWxD
mm / kg
Piping diameter
Liquid / Gas
Inch (mm)
Pipe length range / Elevation difference (in / out)
m/m
Pre-charged pipe length / Additional gas amount
m / g/m
Refrigerant (R32) / CO2 Eq.
kg / T
Operating range
30 / 60
30 / 80
4,20 / 2,835
5,20 / 3,51
Cool Min ~ Max
°C
-15 ~ +46
-15 ~ +46
Heat Min ~ Max
°C
-20 ~ +24
-20 ~ +24
1) EER and COP calculation is based in accordance to EN14511. 2) For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the ηs,c / ηs,h values is
calculated based on EN 14825. 3) Factory setting. 4) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent
6/C/006-97 specification. 5) Add 100 mm for indoor unit or 70 mm for outdoor unit for piping port. * No filter included.
Accessories
Accessories
CZ-RTC6W
CONEX wired remote controller (non-wireless), white
CZ-CAPDC3
Demand control for PACi and Mini ECOi outdoor units
CZ-RTC6WBL
CONEX wired remote controller with Bluetooth®, white
CZ-CAPWFC1
Commercial Wi-Fi Adaptor
CZ-RTC6
CONEX wired remote controller (non-wireless), black
CZ-RTC6BL
CONEX wired remote controller with Bluetooth®, black
PAW-PACR4
Interface to run up to 4 indoor unit groups on backup and
alternative run
CZ-RTC5B
Wired remote controller with Econavi function and datanavi
PAW-GRDBSE20
Outdoor base ground support for noise and vibration absorption
PAW-GRDSTD40
Outdoor elevation platform 400 x 900 x 400 mm
CZ-CENSC1
Econavi energy saving sensor
CZ-RWS3 +
CZ-RWRC3
Infrared remote controller and receiver
Demand response compliant as a standard function
CZ-CAPDC3. This terminal allows demand control of the outdoor unit.
Several setting levels are available:
· Level-1, 2, 3: 75 / 50 / 0%
· Level-1, 2 can be set in 40 - 100% (40, 45, 50…95, 100: each 5%)
CZ-CAPDC3 also allows for forced stop which can be used for fire-alarm
connection on LV3.
Demand
controller
1(L) 2(N)
3
4
1(L)
Terminal block
(supplied as optional kit)
CZ-CAPDC3
R32
-15 °C
-20 °C
COOLING MODE
HEATING MODE
R22
R410A
HIGH EFFICIENCY
COMPRESSOR
BLUEFIN
LARGE FAN
R32
R22 / R410A
RENEWAL
OPTIONAL WI-FI
BMS
CONNECTIVITY
5
YEARS
COMPRESSOR
WARRANTY
INTERNET CONTROL: Optional.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
51