R32
COMMERCIAL INDEX
COMMERCIAL
Wall-mounted Professional -25 °C · R32
· Designed for 24h/7d a week operation
· Wired remote controller, with optional duty rotation mode
· Improved SEER / SCOP to achieve top class energy efficiency
· Aerowings 2.0, for a better control of the airflow
· Built-in Wi-Fi for smart control via Panasonic Comfort Cloud App
· Compatible with Google Assistant and Amazon Alexa
· Chassis and parts designed for easier installation
Kit
KIT-Z25-YKEA
KIT-Z35-YKEA
KIT-Z42-YKEA
KIT-Z50-YKEA
KIT-Z71-YKEA
Cooling capacity
Nominal (Min - Max)
kW
2,50 (0,85 - 3,50)
3,50 (0,85 - 4,20)
4,20 (0,85 - 5,00)
5,00 (0,98 - 6,00)
7,10 (0,98 - 8,50)
EER 1)
Nominal (Min - Max)
W/W
4,90 (4,72 - 3,98)
4,12 (4,72 - 3,68)
3,82 (4,72 - 3,25)
3,68 (3,92 - 3,16)
3,23 (2,33 - 2,83)
9,5 A+++
9,6 A+++
8,6 A+++
8,6 A+++
6,5 A++
kW
2,50
3,50
4,20
5,00
7,10
Nominal (Min - Max)
kW
0,51 (0,18 - 0,88)
0,85 (0,18 - 1,14)
1,10 (0,18 - 1,54)
1,36 (0,25 - 1,90)
2,20 (0,42 - 3,00)
Nominal (Min - Max)
kW
Nominal (Min - Max)
W/W
SEER 2)
Pdesign
Input power
Annual energy consumption 3)
Heating capacity
kWh/a
Heating capacity at -7 °C
92
128
171
203
382
3,40 (0,85 - 5,00)
4,00 (0,85 - 5,80)
5,30 (0,85 - 6,80)
5,80 (0,98 - 8,00)
8,20 (0,98 - 10,20)
kW
COP 1)
3,05
3,40
4,11
4,80
6,31
4,86 (4,72 - 3,97)
4,44 (4,72 - 3,87)
3,93 (4,72 - 3,66)
4,08 (4,26 - 3,35)
3,71 (2,45 - 3,29)
4,1 A+
SCOP 2)
Pdesign at -10 °C
Input power
Nominal (Min - Max)
Annual energy consumption 3)
4,6 A++
4,6 A++
4,5 A+
4,6 A++
kW
2,70
3,20
3,60
4,20
5,50
kW
0,70 (0,18 - 1,26)
0,90 (0,18 - 1,50)
1,35 (0,18 - 1,86)
1,42 (0,23 - 2,39)
2,21 (0,40 - 3,10)
kWh/a
Indoor unit
822
974
1 120
1 278
1 878
CS-Z25YKEA
CS-Z35YKEA
CS-Z42YKEA
CS-Z50YKEA
CS-Z71YKEA
230
Power supply
V
230
230
230
230
Recommended fuse
A
16
16
16
16
20
Connection indoor / outdoor
mm²
4x1,5
4x1,5
4x1,5
4x2,5
4x2,5
11,4 / 13,8
12,7 / 14,8
13,2 / 15,2
17,4 / 19,1
19,0 / 19,9
1,5
2,0
2,4
2,8
4,1
Air flow
Cool / Heat
m³/min
Moisture removal volume
Sound pressure
L/h
4)
Cool (Hi / Lo / Q-Lo)
dB(A)
39 / 25 / 21
42 / 28 / 21
43 / 32 / 29
44 / 37 / 30
47 / 38 / 35
47 / 38 / 35
Heat (Hi / Lo / Q-Lo)
dB(A)
41 / 27 / 22
43 / 30 / 22
44 / 35 / 29
44 / 37 / 30
Sound power
Cool / Heat (Hi)
dB(A)
55 / 57
58 / 59
59 / 60
60 / 60
63 / 63
Dimension
HxWxD
mm
295 x 870 x 229
295 x 870 x 229
295 x 870 x 229
295 x 1 040 x 244
295 x 1 040 x 244
Net weight
kg
Outdoor unit
11
11
11
12
13
CU-Z25YKEA
CU-Z35YKEA
CU-Z42YKEA
CU-Z50YKEA
CU-Z71YKEA
Air flow
Cool / Heat
m³/min
27,6 / 27,6
29,8 / 29,8
29,8 / 31,0
39,8 / 36,9
44,7 / 45,8
Sound pressure 4)
Cool / Heat (Hi)
dB(A)
46 / 48
48 / 50
48 / 51
48 / 50
52 / 54
Sound power
Cool / Heat (Hi)
dB(A)
61 / 63
63 / 65
63 / 66
63 / 65
66 / 68
Dimension 5)
HxWxD
mm
542 x 780 x 289
542 x 780 x 289
542 x 780 x 289
695 x 875 x 320
695 x 875 x 320
30
30
30
40
45
Liquid
Inch (mm)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
1/4 (6,35)
Gas
Inch (mm)
Net weight
kg
Piping diameter
3/8 (9,52)
3/8 (9,52)
1/2 (12,70)
1/2 (12,70)
5/8 (15,88)
Pipe length range
m
3 ~ 20
3 ~ 20
3 ~ 20
3 ~ 30
3 ~ 30
Elevation difference (in / out)
m
15
15
15
15
20
Pre-charged pipe length
m
7,5
7,5
7,5
7,5
10
Additional gas amount
g/m
Refrigerant (R32) / CO2 Eq.
kg / T
Operating range
10
10
10
15
25
0,89 / 0,60
0,89 / 0,60
0,97 / 0,65
1,13 / 0,76
1,35 / 0,91
Cool Min ~ Max
°C
-25 ~ +43
-25 ~ +43
-25 ~ +43
-25 ~ +43
-25 ~ +43
Heat Min ~ Max
°C
-15 ~ +24
-15 ~ +24
-15 ~ +24
-15 ~ +24
-15 ~ +24
1) EER and COP calculation is based in accordance to EN14511. 2) Energy Label Scale from A+++ to D. 3) The annual energy consumption is calculated in accordance to EU/626/2011. 4) The sound pressure of the
indoor unit shows the value measured of a position 1 m in front of the main body and 0,8 m below the unit. For outdoor unit 1 m in front and 1 m in rear side of main body. The sound pressure is measured in
accordance with JIS C 9612. Q-Lo: Quiet mode. Lo: The lowest set fan speed. 5) Add 70 mm for piping port. * Not compatible with PACi NX outdoors and accessories. Domestic range sales conditions may apply.
Check with your sales representative.
Accessories
Accessories
CZ-RCC5
CN-CNT cables x2 for server room application, control of 2
units, rotation, backup, etc.
PAW-WTRAY
Tray for condenser water compatible with outdoor elevation
platform
R32
A+++
9,6 SEER
A++
4,6 SCOP
PAW-GRDBSE20
Outdoor base ground support for noise and vibration
absorption
PAW-GRDSTD40
Outdoor elevation platform 400 x 900 x 400 mm
-25 °C
-15 °C
COOLING MODE
HEATING MODE
R22
R410A
R2 ROTARY
COMPRESSOR
21 dB(A)
AEROWINGS
R32
R22 / R410A
RENEWAL
INTEGRATION
TO S-LINK
BUILT-IN WI-FI
BMS
CONNECTIVITY
SEER: For KIT-Z35-YKEA. SCOP: For KIT-Z25-YKEA, KIT-Z35-YKEA and KIT-Z50-YKEA. SUPER QUIET: For KIT-Z25-YKEA. INTERNET CONTROL: Built-in Wi-Fi.
Rating conditions: Cooling indoor 27 °C DB / 19 °C WB. Cooling outdoor 35 °C DB / 24 °C WB. Heating indoor 20 °C DB. Heating outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.