07 UK HYDRONICS GEN 24 LR - Flipbook - Page 96
R513A
GENERAL INDEX
ECOi-LOOP-N 70-135 H · R513A
Water source heat pumps reversible.
Cooling capacity: 7,0 to 13,3 kW.
Heating capacity: 8,1 to 14,6 kW.
The range at a glance
· 1 version: H (reversible)
· 6 sizes
· Horizontal installation
· Nominal air flow from 1 730 to 3 680 m³/h
· In‑line or perpendicular air flow
· Up to 495 Pa according to size
· Operating range: from 15 °C to 32 °C ambient air
temperature
· Water inlet temperature from 11 °C to 45 °C
Optional controller.
RCS remote control.
Advantages
· Very high performances: EER up to 3,95 and COP up to
4,58
· Low energy consumption EC fan
· Increased robustness: coaxial heat exchanger
· Easy access to the internal components: a wide
removable panel allows an easy access to the electrical
panel and the access to the filter is from the side of the
unit, without removing the return duct
· 100% factory tested
Optional controller.
SRC - mini BMS controller.
SEE PAGE 106 FOR MORE DETAILS ABOUT WATER SOURCE HEAT
PUMPS CONTROL SYSTEMS
Operating limits
Air inlet temperature.
15 °C 1)
24 °C 1)
15 °C
5
10
15
30 °C
20
25
30
35
40
45
50
55
Water inlet temperature.
15 °C
50 °C
10 °C
5
10
35 °C
15
20
25
30
35
40
45
50
1) From 21 to 33 °C DB. * Maximum water pressure 10 bars.
AC SELECT.
Smart and user-friendly the new air conditioning
selection program: https://acselect.panasonic.eu/
96
55
Equipment
· The refrigerant circuit comprises a scroll type hermetic
compressor, a cycle reversal valve, a water/refrigerant
heat exchanger, a bi‑flow thermostatic expansion valve, a
finned coil, HP and LP pressure switches and 2 Schrader
valves (HP and LP)
· The scroll type hermetic compressor, mounted on spring
anti‑vibration mounts, is integrated in a compartment
coated with reinforced acoustic insulation. It is also
equipped with internal thermal protection
· The water/refrigerant heat exchanger is of copper/
stainless steel coaxial type for an increased efficiency
· The units are equipped with a control system (POL423)
utilising Modbus RTU
· The casing is made of galvanised steel sheet.
· Condensate drain pan with an anti‑corrosion treatment
· The electrical box is located inside the compressor
compartment with a wide access panel