07 UK HYDRONICS GEN 24 LR - Flipbook - Page 94
R410A
GENERAL INDEX
ECOi-LOOP 15-30 C/H · R410A
Water source heat pumps cooling only and reversible.
Cooling capacity: 1,5 to 2,9 kW.
Heating capacity: 1,9 to 3,7 kW.
The range at a glance
· 2 versions: C (cooling only) and H (reversible)
· 3 sizes
· Horizontal installation
· Nominal air flow from 435 to 525 m³/h
· Many air and water configurations available
· 140 Pa maximum external static pressure
· Operating range: from 15 °C to 32 °C ambient air
temperature
· Water inlet temperature from 11 °C to 45 °C
Optional controller.
RCS remote control.
Advantages
· Very high performances: EER up to 5,05 and COP up to
5,70
· Low energy consumption EC fan
· In‑line or perpendicular air flow
· Increased robustness: coaxial heat exchanger
· Easy access to the internal components: large electrical
panel and filter accessible from 3 sides
· 100% factory tested
Optional controller.
SRC - mini BMS controller.
SEE PAGE 106 FOR MORE DETAILS ABOUT WATER SOURCE HEAT
PUMPS CONTROL SYSTEMS
Operating limits
Air inlet temperature.
15 °C 1)
23 °C 1)
15 °C
5
10
15
26 °C
20
25
30
35
40
45
50
55
50
55
Water inlet temperature.
16 °C
45 °C
11 °C
5
10
32 °C
15
20
25
30
35
40
45
1) From 21 to 32 °C DB. * Maximum water pressure 10 bars.
AC SELECT.
Smart and user-friendly the new air conditioning
selection program: https://acselect.panasonic.eu/
94
Equipment
· The refrigerant circuit comprises a rotary type hermetic
compressor, a cycle reversal valve (H type only), a water/
refrigerant heat exchanger, a liquid receiver, a capillary
expansion device, a finned coil, HP and LP pressure
switches and 2 Schrader valves (HP and LP)
· The rotary type hermetic compressor, mounted on spring
anti‑vibration mounts, is integrated in a compartment
coated with reinforced acoustic insulation. It is also
equipped with internal thermal protection
· The water/refrigerant heat exchanger is of copper/
stainless steel coaxial type for an increased efficiency
· The units are equipped with a control system (POL423)
utilising Modbus RTU
· The casing is made of galvanised steel sheet
· Condensate drain pan with an anti‑corrosion treatment
· The electrical box is located on the hydraulic service side
with a wide access panel
· The units are equipped with multi‑position brackets for
easy installation