Technical features
Fan coil wall AC fan
P-FW07(IR)
P-FW09(IR)
P-FW18(IR)
P-FW22(IR)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
S2 / S3 / S4 1)
2-pipes, without valve, without/with IR infrared control
Total cooling capacity 2)
kW
1,00 / 1,34 / 1,69
1,58 / 1,79 / 2,50
2,78 / 3,05 / 3,60
2,93 / 3,29 / 4,00
Sensible capacity 2)
kW
0,72 / 0,97 / 1,20
1,21 / 1,37 / 1,87
2,12 / 2,39 / 2,74
2,28 / 2,62 / 3,11
Water flow 2)
l/h
172 / 231 / 291
270 / 308 / 431
479 / 525 / 620
505 / 565 / 687
Water pressure drop 2)
kPa
18,6 / 24,9 / 31,4
18,5 / 21,4 / 31,0
34,6 / 40,0 / 52,3
37,2 / 42,8 / 54,9
3,18 / 3,63 / 4,50
Heating capacity 3)
W
1,42 / 1,62 / 1,72
1,68 / 1,92 / 2,80
2,99 / 3,30 / 4,10
Water flow 3)
l/h
245 / 279 / 296
289 / 331 / 482
515 / 568 / 706
548 / 625 / 775
Water pressure drop 3)
kPa
17,6 / 23,4 / 26,5
21,4 / 23,5 / 28,6
39,9 / 46,3 / 64,7
41,7 / 55,0 / 85,8
Sound levels
Sound power
dB(A)
45 / 49 / 51
40 / 43 / 52
47 / 50 / 54
50 / 55 / 60
Sound pressure 4)
dB(A)
30 / 33 / 35
32 / 36 / 40
39 / 41 / 43
39 / 43 / 48
NR 4)
dB(A)
32 / 36 / 38
34 / 39 / 44
40 / 43 / 46
43 / 46 / 50
1
1
1
1
m³/h
282 / 321 / 360
367 / 413 / 551
532 / 592 / 680
617 / 709 / 850
G1
G1
G1
G1
Ventilation
Number of fans
Air flow
Filter
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
230
230
Single phase
Single phase
Single phase
Single phase
Frequency
Hz
50
50
50
50
Cooling
W
39 / 42 / 62
30 / 33 / 40
44 / 48 / 53
50 / 55 / 69
Heating
W
39 / 42 / 62
27 / 30 / 50
42 / 45 / 60
46 / 51 / 66
Water connections
Connection type
Connections
Gas female threaded
Gas female threaded
Gas female threaded
Gas female threaded
Inch
½
½
½
½
mm
845 x 180 x 275
845 x 180 x 275
940 x 200 x 298
940 x 200 x 298
11
11
13
Dimension and weight
Dimension
LxWxH
Weight
kg
Fan coil wall AC fan
13
P-FW09IR-3W
P-FW22IR-3W
S2 / S3 / S4 1)
S2 / S3 / S4 1)
2-pipes, with valve, with IR infrared control
Total cooling capacity 2)
kW
1,11 / 1,25 / 1,40
2,32 / 2,68 / 3,10
Sensible capacity 2)
kW
0,91 / 1,08 / 1,25
1,68 / 1,98 / 2,28
Water flow 2)
l/h
191 / 215 / 241
400 / 460 / 532
Water pressure drop 2)
kPa
14,9 / 16,8 / 18,8
42,4 / 50,8 / 61,5
2,51 / 2,75 / 3,30
Heating capacity 3)
W
1,29 / 1,61 / 2,00
Water flow 3)
l/h
222 / 277 / 344
432 / 474 / 568
Water pressure drop 3)
kPa
16,1 / 21,3 / 28,2
45,8 / 48,6 / 54,1
Sound levels
Sound power
dB(A)
44 / 50 / 54
53 / 57 / 60
Sound pressure 4)
dB(A)
32 / 36 / 40
39 / 43 / 48
NR 4)
dB(A)
27 / 31 / 37
34 / 37 / 41
1
1
m³/h
150 / 250 / 400
290 / 400 / 600
G1
G1
Ventilation
Number of fans
Air flow
Filter
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
Single phase
Single phase
Frequency
Hz
50
50
Cooling
W
35 / 38 / 43
50 / 58 / 69
Heating
W
30 / 33 / 43
50 / 58 / 69
Water connections
Connection type
Connections
Gas female threaded
Gas female threaded
Inch
½
½
mm
845 x 180 x 275
940 x 200 x 298
11
13
Dimension and weight
Dimension
LxWxH
Weight
kg
1) Fan standard factory set speeds. 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C. 4) Informative
data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A).
ErP
✔
SUPER QUIET
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.
77