07 UK HYDRONICS GEN 24 LR - Flipbook - Page 75
FAN
CHILLERS
COILS
INDEX HYDRONICS AND ROOFTOPS
Technical features
Fan coil cassette EC fan
P-FQ20
P-FQ30
P-FQ40
P-FQ50
P-FQ60
P-FQ70
2V / 6V / 10V 1)
2V / 6V / 10V 1)
2V / 6V / 10V 1)
2V / 6V / 10V 1)
2V / 6V / 10V 1)
2V / 6V / 10V 1)
2-pipes
Total cooling capacity 2)
kW
1,55 / 1,77 / 2,38
1,88 / 2,88 / 4,00
2,79 / 3,51 / 4,71
3,36 / 4,44 / 6,09
3,71 / 5,48 / 7,20
4,05 / 6,51 / 9,61
Sensible capacity 2)
kW
1,30 / 1,49 / 2,00
1,42 / 2,18 / 3,05
2,09 / 2,69 / 3,64
2,53 / 3,36 / 4,49
2,69 / 4,08 / 5,44
2,98 / 4,88 / 7,21
700 / 1 119 / 1 649
Water flow 2)
l/h
267 / 306 / 409
325 / 497 / 688
481 / 604 / 808
579 / 765 / 1 050
640 / 944 / 1 243
Water pressure drop 2)
kPa
4,0 / 5,0 / 10,0
3,0 / 7,0 / 14,0
6,0 / 10,0 / 18,0
7,0 / 12,0 / 22,0
3,0 / 6,0 / 11,0
5,0 / 12,0 / 25,0
Heating capacity 3)
kW
1,92 / 2,17 / 2,74
1,94 / 3,15 / 3,68
3,16 / 3,92 / 5,28
3,80 / 5,08 / 6,84
3,85 / 6,26 / 8,51
4,38 / 7,95 / 11,03
Water flow 3)
l/h
331 / 374 / 472
334 / 543 / 634
544 / 675 / 909
655 / 875 / 1 178
663 / 1 078 / 1 466
754 / 1 369 / 1 900
Water pressure drop 3)
kPa
6,0 / 7,0 / 10,0
3,0 / 9,0 / 11,0
7,0 / 10,0 / 17,0
8,0 / 13,0 / 22,0
3,0 / 8,0 / 14,0
6,0 / 17,0 / 29,0
Total cooling capacity 2)
kW
1,30 / 1,49 / 1,99
2,00 / 2,69 / 3,38
2,56 / 3,23 / 4,02
—
2,99 / 4,98 / 6,65
3,18 / 6,04 / 7,97
Sensible capacity 2)
kW
1,19 / 1,39 / 1,86
1,50 / 2,08 / 2,66
2,04 / 2,60 / 3,32
—
2,25 / 3,79 / 5,08
2,39 / 4,71 / 6,34
Water flow 2)
l/h
234 / 262 / 344
344 / 464 / 581
442 / 556 / 690
—
516 / 858 / 1 144
549 / 1 041 / 1 366
4-pipes
Water pressure drop 2)
kPa
6,0 / 8,0 / 13,0
4,0 / 7,0 / 11,0
6,0 / 10,0 / 15,0
—
5,0 / 14,0 / 24,0
6,0 / 20,0 / 33,0
Heating capacity 4)
kW
1,09 / 1,27 / 1,67
3,10 / 4,40 / 5,46
4,32 / 5,00 / 5,80
—
5,28 / 7,79 / 10,00
6,43 / 10,67 / 13,99
Water flow 4)
l/h
94 / 109 / 144
267 / 379 / 470
372 / 431 / 500
—
455 / 671 / 865
554 / 867 / 1 205
Water pressure drop 4)
kPa
13,0 / 17,0 / 28,0
7,0 / 13,0 / 20,0
13,0 / 17,0 / 23,0
—
4,0 / 7,0 / 11,0
5,0 / 11,0 / 19,0
40 / 52 / 61
Sound levels
Sound power
Sound pressure 5)
NR 5)
2‑pipes
dB(A)
36 / 40 / 49
35 / 44 / 53
42 / 48 / 57
35 / 40 / 49
38 / 46 / 54
4‑pipes
dB(A)
36 / 40 / 49
35 / 44 / 53
42 / 48 / 57
—
38 / 46 / 54
40 / 52 / 61
2‑pipes
dB(A)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
26 / 31 / 40
29 / 37 / 45
31 / 43 / 50
4‑pipes
dB(A)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
—
29 / 37 / 45
31 / 43 / 50
2‑pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
21 / 26 / 35
22 / 32 / 40
25 / 38 / 45
4‑pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
—
22 / 32 / 40
25 / 38 / 45
Ventilation
Number of fans
Air flow
m³/h
Filter
1
1
1
1
1
1
360 / 450 / 659
320 / 504 / 734
486 / 626 / 900
529 / 720 / 979
500 / 824 / 1 159
601 / 1 080 / 1 598
G1
G1
G1
G1
G1
G1
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
230
230
230
230
Single phase
Single phase
Single phase
Single phase
Single phase
Single phase
Frequency
Hz
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
2‑pipes
W
9 / 13 / 29
7 / 14 / 33
13 / 23 / 57
7 / 12 / 25
9 / 23 / 45
11 / 40 / 115
4‑pipes
W
9 / 13 / 29
7 / 14 / 32
13 / 22 / 57
—
9 / 23 / 45
11 / 40 / 115
W
1 500
2 500
2 500
2x1 500
2x1 500
2x1 500
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Electric heater
Water connections
Connection type
2 or 4‑pipes
Cooling
Inch
¾
¾
¾
1
1
1
4‑pipes
Heating
Inch
½
½
½
—
¾
¾
Dimension
With IRYS COANDA 180
LxWxH
mm
595 x 595 x 353
595 x 595 x 353
595 x 595 x 353
849 x 849 x 366
849 x 849 x 366
849 x 849 x 366
With IRYS COANDA 360
LxWxH
mm
595 x 595 x 341
595 x 595 x 341
595 x 595 x 341
849 x 849 x 358
849 x 849 x 358
849 x 849 x 358
With plastic diffuser
LxWxH
mm
720 x 720 x 334
720 x 720 x 334
720 x 720 x 334
960 x 960 x 339
960 x 960 x 339
960 x 960 x 339
14,8
16,5
16,5
37,1
37,1
39,6
Weight
Weight
kg
Energy efficiency class 6)
Fan coil cassette EC fan
2-pipes
4-pipes
FCEER
A to E
B
A
B
A
A
A
FCCOP
A to E
B
B
B
A
A
A
FCEER
A to E
B
A
B
—
A
B
FCCOP
A to E
C
A
B
—
A
A
1) Fan standard factory set speeds (voltage). 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C.
4) According to Eurovent standard. Air: 20 °C, hot water: 65 °C/55 °C. 5) Informative data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A). 6) According to Eurovent.
*** Drain pump and G1 air filter are included as standard.
Accessories and options
Accessories and options
2 way or 3 way valves
Modbus communication board for Plogic
Auxiliary drain pan
Plastic or metallic (IRYS COANDA) diffusers (mandatory)
Ecospeed card for EC fans
SRC ‑ mini BMS controller
Electric heaters (from 1 500 W to 3 000 W)
Plogic controller (other electromechanical or electronic control systems also
available)
Electromechanical sensor for automatic change over
Fresh air intake
G4 filter
TControl EASY 3S and TControl POD glass controllers (other electromechanical or
electronic control systems also available)
IRC: infrared remote control for Plogic
WRC: wall‑mounted remote control for Plogic
ErP
✔
EC MOTOR
GREEN VENTILATION
SUPER QUIET
VERY HIGH
PERFORMANCE
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.
75