Technical features
Fan coil cassette AC fan
P-FQ20
P-FQ30
P-FQ40
P-FQ50
P-FQ60
P-FQ70
R3 / R2 / R1 1)
R3 / R2 / R1 1)
R3 / R2 / R1 1)
R3 / R2 / R1 1)
R3 / R2 / R1 1)
R3 / R2 / R1 1)
2-pipes
Total cooling capacity 2)
kW
1,54 / 1,76 / 2,36
1,87 / 2,87 / 3,99
2,78 / 3,49 / 4,69
3,35 / 4,43 / 6,07
3,69 / 5,46 / 7,18
4,04 / 6,48 / 8,61
Sensible capacity 2)
kW
1,29 / 1,48 / 1,98
1,41 / 2,17 / 3,04
2,08 / 2,67 / 3,62
2,52 / 3,35 / 4,47
2,67 / 4,06 / 5,42
2,97 / 4,85 / 6,34
695 / 1 111 / 1 476
Water flow 2)
l/h
265 / 303 / 404
323 / 493 / 683
478 / 597 / 801
576 / 762 / 1 042
636 / 937 / 1 233
Water pressure drop 2)
kPa
4,0 / 5,0 / 10,0
3,0 / 7,0 / 14,0
6,0 / 10,0 / 18,0
7,0 / 12,0 / 22,0
3,0 / 6,0 / 11,0
5,0 / 12,0 / 20,0
Heating capacity 3)
kW
1,92 / 2,17 / 2,74
1,94 / 3,15 / 3,68
3,16 / 3,92 / 5,28
3,80 / 5,08 / 6,84
3,85 / 6,26 / 8,51
4,38 / 7,95 / 10,28
Water flow 3)
l/h
331 / 374 / 472
334 / 543 / 634
544 / 675 / 909
655 / 875 / 1 178
663 / 1 078 / 1 466
754 / 1 369 / 1 771
Water pressure drop 3)
kPa
6,0 / 7,0 / 10,0
3,0 / 9,0 / 11,0
7,0 / 10,0 / 17,0
8,0 / 13,0 / 22,0
3,0 / 8,0 / 14,0
6,0 / 17,0 / 26,0
Total cooling capacity 2)
kW
1,29 / 1,48 / 1,97
1,99 / 2,68 / 3,37
2,55 / 3,21 / 4,00
—
2,97 / 4,96 / 6,63
3,17 / 6,01 / 7,55
Sensible capacity 2)
kW
1,18 / 1,38 / 1,84
1,49 / 2,07 / 2,65
2,03 / 2,58 / 3,30
—
2,23 / 3,77 / 5,06
2,38 / 4,68 / 5,95
Water flow 2)
l/h
232 / 258 / 359
342 / 465 / 576
437 / 563 / 683
—
511 / 851 / 1 137
543 / 1 030 / 1 294
4-pipes
Water pressure drop 2)
kPa
6,0 / 8,0 / 13,0
4,0 / 7,0 / 11,0
6,0 / 10,0 / 15,0
—
5,0 / 14,0 / 24,0
6,0 / 20,0 / 30,0
Heating capacity 4)
kW
1,09 / 1,27 / 1,67
3,10 / 4,40 / 5,46
4,32 / 5,00 / 5,80
—
5,28 / 7,79 / 10,04
6,43 / 10,07 / 12,77
Water flow 4)
l/h
94 / 109 / 144
267 / 379 / 470
372 / 431 / 500
—
455 / 671 / 865
554 / 867 / 1 100
Water pressure drop 4)
kPa
15,0 / 17,0 / 28,0
7,0 / 13,0 / 20,0
13,0 / 17,0 / 23,0
—
4,0 / 7,0 / 11,0
5,0 / 11,0 / 16,0
40 / 52 / 59
Sound levels
Sound power
Sound pressure 5)
NR 5)
2‑pipes
dB(A)
38 / 42 / 49
35 / 47 / 53
42 / 48 / 57
35 / 40 / 49
38 / 46 / 54
4‑pipes
dB(A)
37 / 41 / 49
35 / 47 / 53
42 / 48 / 57
—
38 / 46 / 54
40 / 52 / 59
2‑pipes
dB(A)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
26 / 31 / 40
29 / 37 / 45
31 / 43 / 50
4‑pipes
dB(A)
27 / 31 / 40
26 / 35 / 44
33 / 39 / 48
—
29 / 37 / 45
31 / 43 / 50
2‑pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
21 / 26 / 35
22 / 32 / 40
25 / 38 / 50
4‑pipes
23 / 27 / 35
20 / 30 / 39
28 / 34 / 43
—
22 / 32 / 40
25 / 38 / 45
Ventilation
Number of fans
Air flow
m³/h
Filter
1
1
1
1
1
1
360 / 450 / 659
320 / 504 / 734
486 / 626 / 900
529 / 720 / 979
500 / 824 / 1 159
601 / 1 080 / 1 447
G1
G1
G1
G1
G1
G1
Electrical data
Voltage
Power supply
V
Phase
Consumption
230
230
230
230
230
230
Single phase
Single phase
Single phase
Single phase
Single phase
Single phase
Frequency
Hz
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
50 / 60
2‑pipes
W
25 / 35 / 58
17 / 34 / 58
38 / 58 / 99
28 / 41 / 66
34 / 61 / 88
44 / 92 / 125
W
25 / 35 / 58
17 / 34 / 58
38 / 58 / 99
—
34 / 61 / 88
44 / 92 / 125
W
1 500
2 500
2 500
2x1 500
2x1 500
2x1 500
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
Gas female
threaded
4‑pipes
Electric heater
Water connections
Connection type
2 or 4‑pipes
Cooling
Inch
¾
¾
¾
1
1
1
4‑pipes
Heating
Inch
½
½
½
—
¾
¾
Dimension
With IRYS COANDA 180
LxWxH
mm
595 x 595 x 353
595 x 595 x 353
595 x 595 x 353
849 x 849 x 366
849 x 849 x 366
849 x 849 x 366
With IRYS COANDA 360
LxWxH
mm
595 x 595 x 341
595 x 595 x 341
595 x 595 x 341
849 x 849 x 358
849 x 849 x 358
849 x 849 x 358
With plastic diffuser
LxWxH
mm
720 x 720 x 334
720 x 720 x 334
720 x 720 x 334
960 x 960 x 339
960 x 960 x 339
960 x 960 x 339
14,8
16,5
16,5
37,1
37,1
39,6
Weight
Weight
kg
Energy efficiency class 6)
Fan coil cassette AC fan
2-pipes
4-pipes
FCEER
A to E
D
C
D
C
C
C
FCCOP
A to E
E
D
D
C
C
D
FCEER
A to E
E
C
D
—
C
D
FCCOP
A to E
E
C
D
—
C
C
1) Fan speeds. 2) According to Eurovent standard. Air: 27 °C DB/19 °C WB, chilled water: 7 °C/12 °C. 3) According to Eurovent standard. Air: 20 °C, hot water: 45 °C/40 °C. 4) According to Eurovent standard. Air:
20 °C, hot water: 65 °C/55 °C. 5) Informative data, considering an hypothetical sound attenuation of the room and installation of 9 dB(A). 6) According to Eurovent. *** Drain pump and G1 air filter are included as
standard.
Accessories and options
Accessories and options
2 way or 3 way valves
Plastic or metallic (IRYS COANDA) diffusers (mandatory)
Auxiliary drain pan
SRC ‑ mini BMS controller
Electric heaters (from 1 500 W to 3 000 W)
Plogic controller (other electromechanical or electronic control systems also
available)
Electromechanical sensor for automatic change over
Fresh air intake
G4 filter
TControl EASY 3S and TControl POD glass controllers (other electromechanical or
electronic control systems also available)
IRC: infrared remote control for Plogic
WRC: wall‑mounted remote control for Plogic
Modbus communication board for Plogic
ErP
✔
SUPER QUIET
ErP compliant following COMMISSION REGULATION (EU) 2016/2281.
73