R410A
GENERAL INDEX
ECOi-W WQ 524-1 604 C/H/R · R410A
Water cooled chillers, heat pumps and condenserless units.
Cooling capacity: 154,3 to 459,8 kW.
Heating capacity: 170,2 to 508,4 kW.
The range at a glance
· 3 versions: C (cooling only), H (heat pump) and R
(condenserless unit)
· 10 sizes
· 2 acoustic options: STD (standard) and S (super low
noise)
Advantages
· High full load efficiency: EER up to 4,50, COP up to 3,90
· High seasonal performances: SEER up to 6,50
· Advanced electronic controller: auto‑adaptive function to
reduce water content in the piping system
· Condensing pressure control option: suitable for well
application
· Wide range of Plug & Play hydrokit: easy hydraulic
installation
· Desuperheater heat exchanger available as option:
heating capacity for free thanks to heat recovery
Equipment
· 2 refrigerant circuits
· Four scroll compressors (tandem)
· Plate evaporator (AISI 316)
· Differential pressure switch
· Electronic expansion valve (standard 1 104‑1 604)
· Phase sequence control
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
Leaving water temperature.
-8 °C 1)
5 °C 1)
5 °C 2)
-10
-5
0
5
18 °C 2)
10
15
25 °C 3)
20
25
30
55 °C 3)
35
40
45
50
55
1) With glycol + EEV.
2) Without glycol + EEV.
3) Only C/H types 20-190.
Note: maximum % glycol (ethylenic or propilenic): 40%.
ECOi-W WQ 524-1 604 C/H/R
Cooling
Leaving water temperature
ΔT
°C
From 3 to 8
Heating
Leaving water temperature
ΔT
°C
From 3 to 15
Accessories and options
Accessories and options
Desuperheater
Soft starter
Hydrokit with 1 or 2 pumps for evaporator and condenser
Water filter
Mechanical gauges
Water flow switch
Modbus communication protocol
AC SELECT.
Smart and user-friendly the new air conditioning
selection program: https://acselect.panasonic.eu/