07 UK HYDRONICS GEN 24 LR - Flipbook - Page 58
R410A
GENERAL INDEX
ECOi-W WQ 20-190 C/H/R · R410A
Water cooled chillers, heat pumps and condenserless units.
Cooling capacity: 21,2 to 192,7 kW.
Heating capacity: 23,7 to 212,3 kW.
The range at a glance
· 3 versions: C (cooling only), H (heat pump) and R
(condenserless unit)
· 14 sizes
· 2 acoustic options: STD (standard) and S (super low
noise)
· 2 frames: F1 (size from 20 to 45) and F2 (size from 50 to
190)
Advantages
· High full load efficiency: EER up to 4,50, COP up to 3,90
· High seasonal performances: SEER up to 6,70
· Compressor box: remarkable sound reduction
· Reduced refrigerant charge: less than 10 kg per circuit
for units up to size 90
· Advanced electronic controller: auto‑adaptive function to
reduce water content in the piping system
· Condensing pressure control option suitable for well
application
· Wide range of Plug & Play hydrokit: easy hydraulic
installation
· DHW function available on the controller with DHW probe
and 3 way valve available as options
· Desuperheater heat exchanger available as option (50‑
190 sizes)
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
Leaving water temperature.
-8 °C 1)
5 °C 1)
5 °C 2)
-10
-5
0
5
18 °C 2)
10
15
25 °C 3)
20
25
30
55 °C 3)
35
40
45
50
1) With glycol + EEV.
2) Without glycol + EEV.
3) Only C/H types 20-190.
Note: maximum % glycol (ethylenic or propilenic): 40%.
55
Equipment
· 1 refrigerant circuit
· 1 or 2 scroll compressors
· Plate evaporator (AISI 316)
· Compressor acoustic box (standard on S)
· Differential pressure switch
· Electronic expansion valve (standard C type 170‑190)
· Phase sequence control
ECOi-W WQ 20-190 C/H/R
Cooling
Leaving water temperature
ΔT
°C
From 3 to 8
Heating 1)
Leaving water temperature
ΔT
°C
From 3 to 15
1) Only C/H types 20-190.
Accessories and options
Accessories and options
Compressor jackets
Power factor corrector capacitors
Desuperheater available for sizes 50‑190
Soft starter
Hydrokit with 1 or 2 pumps for evaporator and condenser
Water filter
Mechanical gauges kit
Water flow switch
Modbus communication protocol
AC SELECT.
Smart and user-friendly the new air conditioning
selection program: https://acselect.panasonic.eu/