07 UK HYDRONICS GEN 24 LR - Flipbook - Page 45
R410A
INDEX HYDRONICS AND ROOFTOPS
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
Power supply
V
Phase
Frequency
Hz
Size
ECOi-W AQUA EVO 140-360 E - condensing
unit
P-
Nominal cooling capacity
400
400
400
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
50
50
50
50
50
50
50
50
140
170
230
260
280
300
330
360
AQAVE0140EA AQAVE0170EA AQAVE0230EA AQAVE0260EA AQAVE0280EA AQAVE0300EA AQAVE0330EA AQAVE0360EA
kW
165
193
250
288
313
337
361
395
Input power 1)
kW
45,7
55,6
74,6
84,4
91,6
99,4
105
117
Sound power 2)
dB(A)
90
90
92
93
93
94
95
95
Sound pressure at 10 m 3)
dB(A)
58
58
60
61
61
62
63
63
140
170
230
260
280
300
330
360
1)
ECOi-W AQUA EVO 140-360 E L - condensing unit
Nominal cooling capacity 1)
kW
159
186
242
279
302
326
351
381
Input power 1)
kW
46,1
56,4
75,4
84,8
92,6
100
105
118
Sound power 2)
dB(A)
85
85
87
88
88
89
90
90
Sound pressure at 10 m 3)
dB(A)
53
53
55
56
56
57
58
58
140
170
230
260
280
300
330
360
ECOi-W AQUA EVO 140-360 E S - condensing unit
Nominal cooling capacity 1)
kW
149
172
225
262
281
305
330
356
Input power 1)
kW
48,5
59,5
80,1
89,6
98,4
107
111
126
Sound power 2)
dB(A)
79
79
82
83
83
85
86
86
Sound pressure at 10 m 3)
dB(A)
47
47
50
51
51
53
54
54
ECOi-W AQUA EVO 140-360 E HT - condensing unit
140
170
230
260
280
300
330
360
Nominal cooling capacity 1)
kW
167
196
253
291
316
341
364
398
Input power 1)
kW
48
57,7
78,2
88,9
95,8
105
111
123
Sound power 2)
dB(A)
92
92
94
96
96
97
98
98
Sound pressure at 10 m 3)
dB(A)
60
60
62
64
64
65
66
66
140
170
230
260
280
300
330
360
Physical features
ECOi-W AQUA EVO 140-360 C/H - cooling
only / heat pump
HxWxL
STD / L
kg
1 157
1 200
1 693
1 890
1 953
2 227
2 345
2 519
Operating
weight ‑ cooling
only
S
kg
1 162
1 205
1 698
1 895
1 958
2 232
2 350
2 524
Operating
weight ‑ heat
pump
mm
2 500 x 1 100 x 2 500 x 1 100 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x
4 000
4 000
3 500
3 500
3 500
4 550
4 550
4 550
Dimension
HT
kg
1 187
1 230
1 743
1 950
2 013
2 297
2 425
2 599
TR
kg
1 342
1 386
2 109
2 379
2 442
2 834
3 018
3 182
STD / L
kg
1 312
1 355
2 078
2 343
2 458
2 702
2 887
3 063
S
kg
1 317
1 360
2 083
2 348
2 463
2 707
2 892
3 068
HT
kg
1 342
1 385
2 128
2 403
2 518
2 772
2 967
3 143
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
2½
2½
3
3
3
3
3
3
140
170
230
260
280
300
330
360
Water connections
Type of water connections (evaporator)
Water inlet/outlet diameter
Inch
ECOi-W AQUA EVO 140-360 E - condensing unit
Dimension
HxWxL
Shipping weight
mm
kg
2 500 x 1 100 x 2 500 x 1 100 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x 2 500 x 2 150 x
4 000
4 000
3 500
3 500
3 500
4 550
4 550
4 550
1 107
1 150
1 542
1 726
1 788
1 946
2 061
2 235
Refrigerant connection
Connection type
To be brazed
To be brazed
To be brazed
To be brazed
To be brazed
To be brazed
To be brazed
To be brazed
Inlet diameter
Inch
1⅝
1⅝
1⅝‑2⅛
1⅝‑2⅛
1⅝‑2⅛
2⅛
2⅛
2⅛
Outlet diameter
Inch
⅞
⅞
⅞‑1⅛
⅞‑1⅛
⅞‑1⅛
1⅛
1⅛
1⅛
1) Data refers to 7 °C leaving chilled water temperature and 35 °C condenser air temperature. 2) Sound levels are at fully loaded conditions. Sound power values refers to ISO 3744 standard. 3) Sound pressures
refer to ISO 3744 standard, parallelepiped shape.
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
45