07 UK HYDRONICS GEN 24 LR - Flipbook - Page 42
R410A
GENERAL INDEX
ECOi-W AQUA EVO 140-360 C/H/E · R410A
Air cooled chillers, heat pumps and condensing units.
Cooling capacity: 144 to 360,7 kW.
Heating capacity: 144,9 to 361,4 kW.
The range at a glance
· 3 versions: C (cooling only), H (heat pump) and E
(condensing unit)
· 8 sizes
· 3 configurations: STD (standard), HT (high temperature)
and HPF (high pressure fan)
· 2 fan types: AC (standard fan) and EC (high efficiency fan)
· 3 acoustic options: STD (standard), L (low noise) and S
(super low noise)
Advantages
· High seasonal performances: SEER up to 4,3
· Common configuration for the different versions: easy
upgrade of the units in stock or on field
· Electronic expansion device: excellent control of
superheating for the best performance at full and partial
load and for a safe operation
· Microchannel coils: significant reduction on refrigerant
charge and operating weight
· Compressor box: remarkable sound reduction even for
the basic noise version
· Control platform: modular architecture, compressor
envelope integration, corrective actions in border line
areas, easy‑friendly user interface
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
ECOi-W AQUA EVO 140-360 C - cooling only
Water
°C
From 5 to 18
Water with glycol*
°C
From ‑10 to 5
Temperature spread
K
From 3 to 7
bar
6
STD
°C
From 5 to 48
L
°C
From 0 to 46
S
°C
From ‑14 to 44
EC‑HT
°C
From ‑18 to 50
External static Standard fans
pressure
High pressure fan (HPF)
Pa
0
Pa