07 UK HYDRONICS GEN 24 LR - Flipbook - Page 40
R410A
GENERAL INDEX
Technical performance
Voltage
Power supply
V
Phase
Frequency
Hz
ECOi-W VL 704-1 204 H HT - heat pump
400
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
50
50
50
50
50
50
704
804
904
1 004
1 104
1 204
Cooling capacity 1)
kW
175,6
199,7
229,5
250,1
276,5
305,6
Input power 1)
kW
66,3
72,4
83,6
87,4
101,1
114,2
2,64
2,75
2,74
2,85
2,73
2,67
3
3
3,1
3,28
3,3
3,23
EER 1)
SEER 2)
ηs,c 2)
117
117
121
128
129
126
Nominal water flow (in the evaporator)
m³/h
30,1
34,3
39,4
42,9
47,5
52,5
Heating capacity 3)
kW
200,7
224,0
256,6
273,7
305,5
341,5
Input power 3)
kW
68,6
71,7
81,8
90,2
103
115
2,93
3,13
3,14
3,04
2,98
2,97
COP 3)
COP 4)
3,66
3,92
3,91
3,79
3,73
3,73
SCOP 2) 5)
ηs,h 2) 5)
3,44
3,40
3,32
3,33
3,37
3,26
Nominal water flow (in the evaporator)
m³/h
135
133
130
130
132
127
34,9
39,0
44,7
47,6
53,2
59,4
100
Sound power 6)
dB(A)
99
99
100
100
100
Sound pressure at 10 m 7)
dB(A)
67
67
68
68
68
68
704
804
904
1 004
1 104
1 204
Size
ECOi-W VL 704-1 204 E STD / HPF - condensing unit
P-VLE0704EA
P-VLE0804EA
P-VLE0904EA
P-VLE1004EA
P-VLE1104EA
P-VLE1204EA
Cooling capacity 8)
kW
199,0
224,0
258,0
283,0
315,0
347,0
Input power 8)
kW
68,7
74,7
86,6
90,6
106
120
Sound power 6)
dB(A)
93
93
94
94
95
95
Sound pressure at 10 m 7)
dB(A)
61
61
62
62
63
63
ECOi-W VL 704-1 204 E L - condensing unit
704
804
904
1 004
1 104
1 204
Cooling capacity 8)
kW
194,0
218,0
251,0
272,5
301,0
330,0
Input power 8)
kW
69,6
76,6
87,8
92,8
109
126
Sound power 6)
dB(A)
87
87
88
88
89
89
Sound pressure at 10 m 7)
dB(A)
55
55
56
56
57
57
ECOi-W VL 704-1 204 E S - condensing unit
704
804
904
1 004
1 104
1 204
Cooling capacity 8)
kW
188,5
211,0
244,0
264,5
292,0
319,0
Input power 8)
kW
72,0
79,5
90,5
95,5
112
131
Sound power 6)
dB(A)
83
83
84
84
85
85
Sound pressure at 10 m 7)
dB(A)
51
51
52
52
53
53
ECOi-W VL 704-1 204 E HT - condensing unit
704
804
904
1 004
1 104
1 204
Cooling capacity 8)
kW
201,0
226,5
261,0
286,5
318,0
353,0
Input power 8)
kW
68,9
74,9
87,1
91,0
105
119
Sound power 6)
dB(A)
99
99
100
100
100
100
Sound pressure at 10 m 7)
dB(A)
67
67
68
68
68
68
1) According EN14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN14825. 3) According EN14511-2013: warm water inlet/outlet temperature:
40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) According EN14511-2013: warm water inlet/outlet temperature: 30/35 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 5) ErP compliant:
following COMMISSION REGULATION (EU) No 813/2013. 6) Sound levels are at fully loaded conditions. Sound power values refers to ISO 3744 standard. 7) Sound pressures refer to ISO 3744 standard,
parallelepiped shape. 8) Data refers to 7 °C leaving chilled water temperature and 35 °C condenser air temperature.
40