07 UK HYDRONICS GEN 24 LR - Flipbook - Page 37
R410A
INDEX HYDRONICS AND ROOFTOPS
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
Power supply
V
Phase
Frequency
Hz
Size
ECOi-W AQV 85-140 E STD / HSE / HPF - condensing unit
400
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
50
50
50
50
50
50
85
95
105
115
125
140
P-AQVE0085EA
P-AQVE0095EA
P-AQVE0105EA
P-AQVE0115EA
P-AQVE0125EA
P-AQVE0140EA
Cooling capacity 1)
kW
92,1
103,2
113,2
121,8
134,7
151,0
Input power 1)
kW
27,4
31,4
34,1
37,0
41,7
46,8
Sound power 2)
dB(A)
84
84
84
84
88
88
Sound pressure at 10 m 3)
dB(A)
53
53
53
53
57
57
ECOi-W AQV 85-140 E STD / HSE S - condensing unit
85
95
105
115
125
140
kW
89
99,5
108,7
116,6
131,6
147,2
Input power 1)
kW
28,6
33,1
36,1
39,3
41,9
47,3
Sound power 2)
dB(A)
82
82
82
82
86
86
Sound pressure at 10 m 3)
dB(A)
51
51
51
51
55
55
Cooling capacity 1)
ECOi-W AQV 85-140 E HT - condensing unit
85
95
105
115
125
140
kW
95
106,8
117,7
127
137,2
153,8
Input power 1)
kW
28,5
32,1
34,4
36,9
41,8
46,7
Sound power 2)
dB(A)
95
95
95
95
95
95
Sound pressure at 10 m 3)
dB(A)
64
64
64
64
64
64
85
95
105
115
125
140
2 185 x 1 095 x
2 555
2 185 x 1 095 x
2 555
2 185 x 1 095 x
2 555
2 185 x 1 095 x
2 555
2 185 x 1 095 x
3 155
2 185 x 1 095 x
3 155
Cooling capacity 1)
Physical features
ECOi-W AQV 85-140 C/H/E - cooling only / heat pump /
condensing unit
Dimension
HxWxL
mm
Operating weight (C type)
STD / HT / S
kg
1058 / 1058 / 1088 1072 / 1072 / 1102 1111 / 1111 / 1141 1143 / 1143 / 1173 1183 / 1183 / 1213 1262 / 1262 / 1292
Operating weight (H type)
STD / HT / S
kg
1090 / 1090 / 1120 1105 / 1105 / 1135 1149 / 1149 / 1179 1180 / 1180 / 1210 1227 / 1227 / 1257 1301 / 1301 / 1331
Shipping weight (E type)
STD / S
kg
971 / 1 001
983 / 1 013
1 013 / 1 043
1 043 / 1 073
1 066 / 1 096
1 142 / 1 172
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
Male gas
threaded
2½
2½
2½
2½
2½
2½
To be brazed
Water connections (85-140 C/H types)
Type of water connections (evaporator)
Water inlet/outlet diameter
Inch
Condenser (85-140 E type)
Connection type
To be brazed
To be brazed
To be brazed
To be brazed
To be brazed
Inlet diameter
Inch
⅝
⅝
⅝
⅝
⅞
⅞
Outlet diameter
Inch
1⅜
1⅜
1⅜
1⅜
1⅜
1⅜
1) Data refers to 7 °C leaving chilled water temperature and 35 °C condenser air temperature, according EN14511-2013 standard. 2) Sound levels are at fully loaded conditions. Sound power values refers to ISO
3744 standard. 3) Sound pressures refer to ISO 3744 standard, parallelepiped shape.
Special inverter fan.
Option.
Bluefin coil.
As standard on H
models.
True dual circuit
evaporator.
Optimised heat
transfer coefficient.
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
3 pump option.
Energy saving in
partial load.
37