07 UK HYDRONICS GEN 24 LR - Flipbook - Page 33
R32
INDEX HYDRONICS AND ROOFTOPS
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
Power supply
V
Phase
Frequency
400
400
Three phase
Three phase
Hz
50
50
150
170
P-AQAZ0150CA
P-AQAZ0170CA
Size
ECOi-W AQUA-Z 150-170 C - cooling only
Cooling capacity 1)
kW
154
173
Input power 1)
kW
47,4
55,7
EER (STD AC / STD EC) *1)
3,25 / 3,38
3,11 / 3,20
SEER (STD AC / STD EC) *2) 3)
ηs,c (STD AC / STD EC) *2) 3)
4,70 / 5,22
4,68 / 5,16
184,8 / 205,6
184,2 / 203,2
Nominal water flow (in the evaporator)
m³/h
27,2
30,7
Sound power (STD AC / S) *
dB(A)
89 / 86
91 / 88
Sound pressure at 10 m (STD AC / S) *4)
dB(A)
ECOi-W AQUA-Z 150-170 H - heat pump
57 / 54
59 / 56
P-AQAZ0150HA
P-AQAZ0170HA
Cooling capacity 1)
152
170
Input power 1)
47,9
57,1
EER (STD AC / STD EC) *1)
3,17 / 3,30
2,98 / 3,07
EER (STD AC / STD EC) *5)
3,63 / 3,76
3,39 / 3,56
SEER (STD AC / STD EC) *2)
ηs,c (STD AC / STD EC) *2)
4,59 / 5,04
4,49 / 4,92
180,5 / 198,7
176,6 / 193,8
Nominal water flow (in the evaporator)
m³/h
27,2
30,7
Heating capacity 6)
kW
159,1
180,1
Input power 6)
kW
COP (STD AC / STD EC) *6)
48,2
54,5
3,30 / 3,48
3,31 / 3,40
COP (STD AC / STD EC) *7)
4,07 / 4,31
4,02 / 4,16
SCOP (STD AC / STD EC) *2) 8)
3,57 / 4,04
3,60 / 3,95
Energy efficiency class (STD AC / STD EC) *2) 7)
ηs,h (STD AC / STD EC) *2) 7)
A+++ to D
—/—
—/—
139,9 / 158,4
140,9 / 155,2
Nominal water flow (in the evaporator)
m³/h
27,5
31,7
Sound power (STD AC / S) *
dB(A)
89 / 86
91 / 88
Sound pressure at 10 m (STD AC / S) *4)
dB(A)
57 / 54
59 / 56
Physical features
ECOi-W AQUA-Z 150-170 C/H - cooling only / heat pump
Dimension
150
170
2 285 / 2 333
2 285 / 2 333
Height (STD / EC/HPF)
mm
Width
mm
1 151
1 151
Length without water tank
mm
3 789
3 789
kg
1 265
1 279
Male gas threaded BSPP ISO 228
Male gas threaded BSPP ISO 228
2½
2½
Operating weight without water tank ‑ 1 pump
Water connections
Type of water connections (evaporator)
Water inlet/outlet diameter
Inch
1) According EN14511-2018: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN14825. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 5) According EN14511-2018: chilled water inlet/outlet temperature: 23/18 °C, outdoor ambient temperature 35 °C DB.
6) According EN14511-2018: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 7) According EN14511-2018: warm water inlet/outlet temperature: 30/35 °C,
outdoor ambient temperature 7 °C DB/6 °C WB. 8) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013.
* STD AC: standard version with AC fan, STD EC: standard version with high efficiency EC fan, S: super low noise version with high efficiency EC fan + compressor sound jackets.
Accessories and options
Accessories and options
Accessories and options
Additional external switch (cooling/heating) (H type
only)
Energy meter for Input power
Shut off valves
High efficiency EC fan
Sofstarter
Anti‑vibration rubber mount / spring dampers
High pressure fan (HPF)
SRC ‑ mini BMS controller
Compressor jackets (standard for S versions)
Outdoor coil protection grid
Super low noise (S): EC fan + compressor jackets
Contact for external general alarm
Power factor corrector capacitors
Variable or fixed speed pumps
Desuperheater
Refrigerant gauges HP/LP
Water pressure switch
Electrical heater for the water tank (H type only)
Remote control kit
Water tank 300 l
R32
ErP
✔
HIGH
SEER
HIGH
SCOP
5,22
4,08
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
SUPER QUIET
VERY HIGH
PERFORMANCE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.