07 UK HYDRONICS GEN 24 LR - Flipbook - Page 31
R32
INDEX HYDRONICS AND ROOFTOPS
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
Power supply
V
Phase
Frequency
Hz
Size
400
400
400
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
50
50
50
50
50
50
50
50
50
60
70
75
85
100
115
130
ECOi-W AQUA-Z 50-130 C - cooling only
P-
Cooling capacity 1)
kW
AQAZ0050CA AQAZ0060CA AQAZ0070CA AQAZ0075CA AQAZ0085CA AQAZ0100CA AQAZ0115CA AQAZ0130CA
51,6
57,6
69,7
78,2
82,8
100
116
126
Input power 1)
kW
16,5
19,6
22,4
24
26,8
31,4
37,4
42,3
EER (STD AC / STD EC) *1)
3,13 / 3,25
2,94 / 3,03
3,11 / 3,29
3,26 / 3,41
3,09 / 3,23
3,18 / 3,30
3,10 / 3,20
2,98 / 3,07
SEER (STD AC / STD EC) *2) 3)
ηs,c (STD AC / STD EC) *2) 3)
4,60 / 5,05
4,59 / 5,02
4,61 / 5,31
4,72 / 5,29
4,45 / 4,96
4,88 / 5,19
4,59 / 5,01
4,43 / 4,71
180,9 / 198,9 180,5 / 197,8 181,3 / 209,6 185,6 / 208,7 175,0 / 195,6 192,3 / 204,9 180,5 / 197,3 174,2 / 185,6
Nominal water flow (in the evaporator)
m³/h
9,2
10,6
12,2
13,2
14,7
17,9
21,1
23,5
Sound power (STD AC / S) *
dB(A)
83 / 81
84 / 81
81 / 78
81 / 78
84 / 82
86 / 83
87 / 84
87 / 84
Sound pressure at 10 m (STD AC / S) *4)
dB(A)
51 / 49
52 / 49
50 / 47
49 / 46
52 / 50
54 / 51
55 / 52
55 / 53
ECOi-W AQUA-Z 50-130 H - heat pump
P-
AQAZ0050HA AQAZ0060HA AQAZ0070HA AQAZ0075HA AQAZ0085HA AQAZ0100HA AQAZ0115HA AQAZ0130HA
Cooling capacity 1)
51,1
57
69
77,4
82
99,3
115
125
Input power 1)
16,7
19,8
22,6
24,3
27,1
31,8
37,7
42,7
EER (STD AC / STD EC) *1)
3,06 / 3,17
2,88 / 2,97
3,05 / 3,22
3,19 / 3,35
3,03 / 3,17
3,12 / 3,25
3,05 / 3,14
2,93 / 3,00
EER (STD AC / STD EC) *5)
3,53 / 3,67
3,40 / 3,50
3,57 / 3,64
3,78 / 3,96
3,52 / 3,66
3,63 / 3,76
3,51 / 3,54
3,39 / 3,50
4,46 / 4,83
4,42 / 4,50
4,51 / 5,04
4,61 / 4,99
4,33 / 4,80
4,77 / 4,93
4,44 / 4,82
SEER (STD AC / STD EC) *2)
ηs,c (STD AC / STD EC) *2)
175,2 / 190,2 173,6 / 176,9 177,5 / 198,8 181,5 / 196,7 170,3 / 188,9 187,7 / 194,1 174,6 / 190,0
4,23 / 4,51
166 / 177,2
Nominal water flow (in the evaporator)
m³/h
8,7
10,6
12,2
13,2
14,7
17,9
21,1
23,5
Heating capacity 6)
kW
51,7
59,7
71,8
78,5
86,5
107,6
122,3
137,5
Input power 6)
kW
16,5
19,3
22,1
24,2
27,2
32,5
37,0
41,0
COP (STD AC / STD EC) *6)
3,12 / 3,27
3,10 / 3,21
3,24 / 3,43
3,24 / 3,41
3,19 / 3,30
3,31 / 3,45
3,31 / 3,42
3,36 / 3,42
COP (STD AC / STD EC) *7)
3,81 / 4,00
3,80 / 3,92
3,92 / 4,21
3,91 / 4,16
3,92 / 4,16
3,99 / 4,19
4,10 / 4,26
4,04 / 4,12
SCOP (STD AC / STD EC) *2) 8)
3,53 /3,90
3,54 / 3,94
3,47 / 3,71
3,65 / 3,80
3,60 / 4,02
3,64 / 4,10
3,66 / 4,02
3,72 / 3,97
Energy efficiency class (STD AC / STD EC) *2) 7) A+++ to D
A+ / A+
A+ / A+
A+ / A++
A+ / A++
A+ / A++
—/—
—/—
—/—
ηs,h (STD AC / STD EC) *2) 7)
138,0 / 152,8 138,5 / 154,5 135,6 / 145,3 143,2 / 148,8 141,2 / 157,8 142,5 / 160,9 143,2 / 157,9 145,7 / 155,9
Nominal water flow (in the evaporator)
m³/h
9,3
10,7
12,5
13,9
15,0
18,3
21,5
23,9
Sound power (STD AC / S) *
dB(A)
83 / 81
84 / 81
81 / 78
81 / 78
84 / 82
86 / 83
87 / 84
87 / 84
Sound pressure at 10 m (STD AC / S) *4)
dB(A)
51 / 49
52 / 49
50 / 47
50 / 46
52 / 50
54 / 51
55 / 52
56 / 53
Physical features
ECOi-W AQUA-Z 50-130 C/H - cooling only / heat pump
Height (STD / EC/HPF)
Dimension
mm
50
60
70
75
85
100
115
130
1 986 / 2 034
1 986 / 2 034
1 986 / 2 034
1 986 / 2 034
2 286 / 2 334
2 286 / 2 334
2 286 / 2 334
2 286 / 2 334
Width
mm
1 160
1 160
1 160
1 160
1 160
1 160
1 160
1 160
Length without water tank
mm
2 180
2 180
2 180
2 180
2 180
2 180
2 180
2 180
527
547
621
637
701
731
813
815
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
Male gas
threaded
BSPP ISO
228
2
2
2
2
2½
2½
2½
2½
Operating weight without water tank ‑ 1 pump kg
Water connections
Type of water connections (evaporator)
Water inlet/outlet diameter
Inch
1) According EN14511-2018: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN14825. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 5) According EN14511-2018: chilled water inlet/outlet temperature: 23/18 °C, outdoor ambient temperature 35 °C DB.
6) According EN14511-2018: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 7) According EN14511-2018: warm water inlet/outlet temperature: 30/35 °C,
outdoor ambient temperature 7 °C DB/6 °C WB. 8) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013.
* STD AC: standard version with AC fan, STD EC: standard version with high efficiency EC fan, S: super low noise version with high efficiency EC fan + compressor sound jackets.
Accessories and options
Accessories and options
Accessories and options
Additional external switch (cooling/heating) (H type
only)
High efficiency EC fan
SRC ‑ mini BMS controller
High pressure fan (HPF)
Super low noise (S): EC fan + compressor jackets
Anti‑vibration rubber mount / spring dampers
Outdoor coil protection grid
Variable or fixed speed pumps
Compressor jackets (standard for S versions)
Power factor corrector capacitors
Water pressure switch
Contact for external general alarm
Refrigerant gauges HP/LP
Water tank 300 l
Desuperheater
Remote control kit
Without neutral
Electrical heater for the water tank (H type only)
Shut off valves
Energy meter for Input power
Sofstarter
R32
ErP
✔
HIGH
SEER
HIGH
SCOP
5,04
4,10
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
SUPER QUIET
VERY HIGH
PERFORMANCE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
31