07 UK HYDRONICS GEN 24 LR - Flipbook - Page 30
R32
GENERAL INDEX
ECOi-W AQUA-Z 50-130 C/H · R32
R32
Air cooled chillers and heat pumps.
REFRIGERANT
Cooling capacity: 51,6 to 126 kW.
Heating capacity: 51,7 to 137,5 kW.
The range at a glance
· 2 versions: C (cooling only) and H (heat pump)
· 8 sizes
· SEER up to 4,88 (STD AC) / 5,31 (STD EC)
· SCOP up to 3,72 (STD AC) / 4,10 (STD EC)
· 2 configurations: STD (standard) and HPF (high pressure
fan)
· 2 fan types: AC (standard fan) and EC (high efficiency fan)
· 2 acoustic options: STD (standard) and S (super low
noise)
Advantages
· Sustainable units: R32 refrigerant (GWP= 675)
· Very high efficiency
· Wide operating limits
· Low footprint: only 2,53 m²
· Reduced sound levels: S version (super low noise) with
EC fan and compressor sound jackets
· New advanced control system
· Easy maintenance: great accessibility to the internal
components
· Cascade controller available for multi‑system operation
· SG ready
· 100% factory tested
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
Ambient temperature.
-15 °C
48 °C
-15 °C
-20
-15
40 °C
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
Leaving water temperature.
-10 °C 1)
18 °C
20 °C
-20
-15
-10
-5
0
5
10
15
20
25
55 °C
30
35
40
45
1) With glycol, 5 °C without glycol.
AC SELECT.
Smart and user-friendly the new air conditioning
selection program: https://acselect.panasonic.eu/
30
50
55
Equipment
· 1 refrigerant circuit with tandem scroll compressors for
a higher efficiency at partial load
· Stainless steel plate heat exchanger insulated with
closed cell synthetic foam
· Finned coil condenser constructed with seamless copper
tubes mechanically expanded into aluminium fins ‑
Bluefin treatment for H type
· Hydraulic circuit without pump
· Complete integrated control system with an external
control panel that displays the operating parameters and
alarms
· Modbus RTU, Modbus TCP/IP, BACnet MSTP or BACnet
IP
· Night mode for energy savings and reduced sound levels
· Electronic expansion valve
· Water compensation curve control
· Return and leaving water temperature control
· External switch (cooling/heating, night mode, load
shedding)
· Water filter and water flow switch
· Phase sequence monitor