07 UK HYDRONICS GEN 24 LR - Flipbook - Page 29
R410A
INDEX HYDRONICS AND ROOFTOPS
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
Power supply
V
Phase
Frequency
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Hz
Size
ECOi-W AQUA 140-210 C - cooling only
50
50
50
50
50
140
150
170
190
210
P-AQAE0210CA
P-AQAE0140CA
P-AQAE0150CA
P-AQAE0170CA
P-AQAE0190CA
Cooling capacity 1)
kW
132
146
164
181
208
Input power 1)
kW
43,1
47,6
54,8
61,1
69,8
EER 1)
3,06
3,07
2,99
2,96
2,98
SEER 2) 3)
ηs,c 2) 3)
4,40
4,45
4,38
4,40
4,25
Nominal water flow (in the evaporator)
m³/h
173
175
172
173
167
22,7
25,1
28,2
31,1
35,8
Sound power (STD fan)
dB(A)
85
85
87
88
88
Sound pressure at 10 m (STD fan) 4)
dB(A)
53,4
53,4
55,0
56,1
56,1
P-AQAE0210HA
ECOi-W AQUA 140-210 H - heat pump
P-AQAE0140HA
P-AQAE0150HA
P-AQAE0170HA
P-AQAE0190HA
Cooling capacity 1)
kW
128
142
164
178
208
Input power 1)
kW
43,2
47,7
54,7
61,3
69,7
EER 1)
2,97
2,98
3,00
2,90
2,98
SEER 2)
ηs,c 2)
4,39
4,36
4,31
4,23
4,28
173
171
169
166
168
21,6
23,7
25,9
30,2
33,7
Nominal water flow (in the evaporator)
m³/h
Heating capacity 5)
kW
144
154
170
195
218
Input power 5)
kW
45,8
50,2
55,4
67,5
78,3
COP 5)
3,14
3,06
3,07
2,89
2,78
COP 6)
3,84
3,82
3,81
3,82
3,82
SCOP 2) 7)
ηs,h 2) 7)
3,30
3,33
3,30
3,28
3,23
Nominal water flow (in the evaporator)
m³/h
129
130
129
128
126
24,8
26,5
29,6
33,9
37,9
Sound power
dB(A)
85
85
87
88
88
Sound pressure at 10 m (STD fan) 4)
dB(A)
53,4
53,4
55
56,1
56,1
140
150
170
190
210
Height
mm
2 295
2 295
2 321
2 321
2 321
Width
mm
2 210
2 210
2 210
2 210
2 210
Length w/o / w water tank
mm
2 856 / 3 666
2 856 / 3 666
2 856 / 3 666
2 856 / 3 666
2 856 / 3 666
kg
1 685 / 2 139
1 705 / 2 159
1 798 / 2 253
1 891 / 2 343
2 201 / 2 653
Victaulic®
Victaulic®
Victaulic®
Victaulic®
Victaulic®
2½
2½
2½
2½
2½
Physical features
ECOi-W AQUA 140-210 C/H - cooling only / heat pump
Dimension
Operating weight w/o / w water tank ‑ 1 pump
Water connections
Type of water connections (evaporator)
Water inlet/outlet diameter
Inch
1) According EN14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN14825. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 5) According EN14511-2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB.
6) According EN14511-2013: warm water inlet/outlet temperature: 30/35 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 7) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013.
* w/o: without, w: with.
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers
Modbus TCP/IP
SRC ‑ mini BMS controller
BACnet IP and BACnet MSTP
Outdoor coil protection grid
Variable or fixed* speed pumps
Desuperheater (upon request)
Nordic pack (H type only)
Water tank 300 l
Fan speed control
Refrigerant gauges HP/LP
Without neutral
Finned coil blygold treatment (upon request) and
epoxy
Remote control
Water pressure switch
Hydraulic gauges
Soft starter
Shut off valves
* ECOi-W AQUA C units can’t be Ecodesign compliant with this option.
ErP
✔
HIGH
SEER
HIGH
SCOP
4,40
3,36
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
SUPER QUIET
VERY HIGH
PERFORMANCE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
29