07 UK HYDRONICS GEN 24 LR - Flipbook - Page 27
R410A
INDEX HYDRONICS AND ROOFTOPS
CHILLERS AND HEAT PUMPS
Technical performance
Voltage
Power supply
V
Phase
Frequency
Hz
Size
ECOi-W AQUA 45-125 C - cooling only
400
400
400
400
400
400
400
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
Three phase
50
50
50
50
50
50
50
45
55
65
75
90
105
125
P-AQAE0045CA P-AQAE0055CA P-AQAE0065CA P-AQAE0075CA P-AQAE0090CA P-AQAE0105CA P-AQAE0125CA
Cooling capacity 1)
kW
45,3
52,0
66,1
73,1
90,9
104,0
Input power 1)
kW
15,4
17,6
21,7
24,0
30,7
34,9
40,6
EER 1)
2,95
2,96
3,05
3,05
2,96
2,98
3,03
SEER 2) 3)
ηs,c 2) 3)
4,40
4,53
4,53
4,68
4,45
4,50
4,55
173
178
178
184
175
177
179
7,8
8,9
11,4
12,6
15,6
17,9
21,2
Nominal water flow (in the evaporator)
m³/h
123,0
Sound power (STD fan)
dB(A)
81
81
81
81
84
84
84
Sound pressure at 10 m (STD fan) 4)
dB(A)
48,8
48,8
48,8
48,8
51,8
51,8
51,8
ECOi-W AQUA 45-125 H - heat pump
P-AQAE0045HA P-AQAE0055HA P-AQAE0065HA P-AQAE0075HA P-AQAE0090HA P-AQAE0105HA P-AQAE0125HA
Cooling capacity 1)
kW
44,3
50,9
64,1
71,0
88,7
101,0
Input power 1)
kW
15,9
18,0
21,8
24,0
30,6
34,8
40,4
EER 1)
2,78
2,83
2,94
2,95
2,90
2,90
2,96
SEER 2)
ηs,c 2)
4,20
4,41
4,51
4,63
4,40
4,44
4,49
165
174
177
182
173
175
177
8,0
9,2
11,3
12,3
15,7
18,2
20,9
119,0
Nominal water flow (in the evaporator)
m³/h
119,0
Heating capacity 5)
kW
48,5
58,2
67,3
76,0
88,2
101,0
Input power 5)
kW
17,3
20,4
22,5
24,3
33,8
38,4
45,5
2,80
2,86
2,99
3,12
2,61
2,63
2,62
COP 5)
COP 6)
3,89
3,83
3,80
3,82
3,80
3,80
3,82
SCOP 2) 7)
3,38
3,38
3,55
3,53
3,40
3,43
3,43
Energy efficiency class 2) 7)
ηs,h 2) 7)
A+++ to D
A+
A+
A+
A+
—
—
—
132
132
139
138
133
134
134
Nominal water flow (in the evaporator)
Sound power (STD fan)
m³/h
8,4
10,2
11,7
13,2
15,3
17,6
20,7
dB(A)
81
81
81
81
84
84
Sound pressure at 10 m (STD fan) 4)
84
dB(A)
48,8
48,8
48,8
48,8
51,8
51,8
51,8
ECOi-W AQUA 45-125 E - condensing unit
P-AQAE0045EA P-AQAE0055EA P-AQAE0065EA P-AQAE0075EA P-AQAE0090EA P-AQAE0105EA P-AQAE0125EA
Cooling capacity 8)
kW
57,4
64,5
72,4
79,3
104,0
120,0
Input power 8)
kW
19,5
22,3
24,4
27,2
39,3
43,0
51,3
2,94
2,89
2,97
2,91
2,65
2,79
2,66
80
80
80
80
83
83
83
EER 8)
Sound power
dB(A)
136,0
Physical features
ECOi-W AQUA 45-125 C/H - cooling only / heat pump
Dimension
45
55
65
75
90
105
125
1 986 / 2 025
1 986 / 2 025
1 986 / 2 026
1 986 / 2 026
2 286 / 2 379
2 286 / 2 379
2 286 / 2 379
Height (STD / HPF)
mm
Width
mm
1 160
1 160
1 160
1 160
1 160
1 160
1 160
Length w/o / w water tank
mm
2 180 / 2 680
2 180 / 2 680
2 180 / 2 680
2 180 / 2 680
2 180 / 2 680
2 180 / 2 680
2 180 / 2 680
545 / 1 010
545 / 1 010
615 / 1 080
615 / 1 080
795 / 1 260
905 / 1 370
925 / 1 390
Operating weight w/o / w water tank ‑ 1 pump kg
Water connections
Male gas
Male gas
Male gas
Male gas
Male gas
Male gas
Male gas
threaded BSPP threaded BSPP threaded BSPP threaded BSPP threaded BSPP threaded BSPP threaded BSPP
ISO 228
ISO 228
ISO 228
ISO 228
ISO 228
ISO 228
ISO 228
Type of water connections (evaporator)
Water inlet/outlet diameter
Inch
ECOi-W AQUA 45-125 E - condensing unit
Operating weight
Dimension
kg
HxWxD
mm
2
2
2
2
2½
2½
2½
45
55
65
75
90
105
125
490
490
560
560
740
850
870
1 986 x 1 160 x
2 180
1 986 x 1 160 x
2 180
1 986 x 1 160 x
2 180
1 986 x 1 160 x
2 180
2 286 x 1 160 x
2 180
2 286 x 1 160 x
2 180
2 286 x 1 160 x
2 180
Refrigerant connections
Liquid line
Inch
⅝
⅝
⅝
⅝
⅞
⅞
⅞
Suction line
Inch
1⅝
1⅝
1⅝
1⅝
1⅝
1⅝
1⅝
1) According EN14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN14825. 3) ErP compliant: following COMMISSION REGULATION (EU)
2016/2281. 4) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 5) According EN14511-2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB.
6) According EN14511-2013: warm water inlet/outlet temperature: 30/35 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 7) ErP compliant: following COMMISSION REGULATION (EU) No 813/2013. 8) Data
refers to 7 °C leaving chilled water temperature and 35 °C condenser air temperature, according EN14511-2013 standard.
* w/o: without, w: with.
Accessories and options
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers
Shut off valves
BACnet IP or BACnet MSTP
Super low noise (S): acoustic box around the
compressors
Desuperheater
High pressure fan (HPF)
SRC ‑ mini BMS controller
Fan speed control
Modbus TCP/IP
Variable or fixed* speed pumps
Finned coil blygold treatment (upon request) or epoxy
Outdoor coil protection grid
Water tank 300 l
Electrical heater high or low power (H type only)
Refrigerant gauges HP/LP
Without neutral (upon request)
Remote control
Water pressure switch
Soft starter
* Not available with ECOi-W AQUA C units due to Ecodesign compliance.
ErP
✔
HIGH
SEER
HIGH
SCOP
4,41
3,43
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
SUPER QUIET
VERY HIGH
PERFORMANCE
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
27